Stop the chiller-heater
Press the
STOP
button on the main screen of the control panel. To stop the chiller-heater from a
remote location, enter the remote stop signal.
When the chiller-heater stops, the following occurs:
• The capacity control valves close.
• Combustion stops.
• Close the fuel supply valve manually.
• The dilution operation starts. It continues for 7 - 30 minutes.
• During the dilution operation, the solution circulation pump, and the refrigerant pump operate.
• When the dilution operation is complete, the solution circulation pump, and the refrigerant pump
stop. Then, the chilled/hot water pump, the cooling water pump, and the cooling tower fan stop.
Interlocking procedure
Operating the chiller-heater in cooling mode without the air conditioner running can cause the
chilled water to freeze. If the unit contains one air conditioner only, secure the air conditioner
interlock.
87
Model YHAU-CGN/H-CXR(M)Double Effect Direct Fired Small Absorption Chiller-Heater