Communication data
Table 19: Read command
Item
Display
Unit
Address
Content
1
Set Point (Chilled/Hot water
outlet temp.)
44.6
7
°F
°C
00001
0050~1000 unit, 1 unit=0.1°F (0.1°C)
2
Automatic stop temp. at cooling
mode (thermo-off temp)
41.0
5
°F
°C
00003
0040~1000 unit, 1 unit=0.1°F (0.1°C)
3
Temp. difference of Automatic
start/stop control at cooling
mode
41.0
5
°F
°C
00005
0001~1000 unit, 1 unit=0.1°F (0.1°C)
4
Automatic stop temp. at heating
mode (thermo-off temp)
143.6
62.0
°F
°C
00007
0040~1000 unit, 1 unit=0.1°F (0.1°C)
Set value
5
Temp. difference of Automatic
start/stop control at heating
mode
41.0
5
°F
°C
00009
0001~1000 unit, 1 unit=0.1°F (0.1°C)
6
Operation condition
0 or 1 or 2
-
00021
0: Stop
1: Cooling operation
2: Heating operation
7
Local/Remote mode condition
0 or 1
-
01001
0: Local
1: Remote
8
Solution pump condition
0 or 1
-
01003
0: Stop
1: Operation
9
Refrigerant pump condition
0 or 1
-
01005
0: Stop
1: Operation
10
Burner fan condition
0 or 1
-
01007
0: Stop
1: Operation
11
Load limit condition
0 or 1
-
01009
0: Normal operation
1: Load limit operation
12
Control manipulated variable
100
%
00023
-0100~1100 unit, 1 unit=0.1%
13
Failure signal
0 or 1
-
01011
0: Normal operation
1: Failure occur
Operation condition
14
Alarm signal
0 or 1
-
01013
0: Normal operation
1: Alarm occur
15
Chilled/Hot water inlet temp.
53.6
12
°F
°C
00083
0001~4000 unit, 1 unit=0.1°F (0.1°C)
16
Chilled/Hot water outlet temp.
44.6
7
°F
°C
00085
0001~4000 unit, 1 unit=0.1°F (0.1°C)
17
Refrigerant temp. at evaporator
41.0
5
°F
°C
00087
0001~4000 unit, 1 unit=0.1°F (0.1°C)
18
Cooling water inlet temp.
89.6
32
°F
°C
00089
0001~4000 unit, 1 unit=0.1°F (0.1°C)
19
Cooling water outlet temp.
98.6
37
°F
°C
00091
0001~4000 unit, 1 unit=0.1°F (0.1°C)
20
Absorber solution temp.
100.4
38
°F
°C
00093
0001~4000 unit, 1 unit=0.1°F (0.1°C)
21
High temperature generator
solution temp.
293.0
145
°F
°C
00095
0001~4000 unit, 1 unit=0.1°F (0.1°C)
22
Exhaust gas temp.
428.0
226
°F
°C
00097
0001~4000 unit, 1 unit=0.1°F (0.1°C)
23
High temperature generator
pressure
10.15
70.0
mmHg
kPa
00099
0001~1100 unit, 1 unit=0.1 mmHg (0.1 kPa)
24
Motor opening rate
100.0
%
00101
0001~1100 unit, 1 unit=0.1%
25
High temperature generator
concentration
62.0
%
00103
0001~1100 unit, 1 unit=0.1%
Measurement value
26
Purge tank pressure
15
2.0
mmHg
kPa
00105
0001~4000 unit, 1 unit=0.1 mmHg (0.1 kPa)
Model YHAU-CGN/H-CXR(M)Double Effect Direct Fired Small Absorption Chiller-Heater