![Johnson Controls York YHAU-C Installation, Operation And Maintenance Manual Download Page 151](http://html1.mh-extra.com/html/johnson-controls/york-yhau-c/york-yhau-c_installation-operation-and-maintenance-manual_2023471151.webp)
Figure 70: Process and instrumentation diagram for EXE series chiller
Valve operation/location
Purging pattern
Use
Operation
V10, V11
V13, V16
V14
V21
V20
A
Check capacity of vacuum pump
–
×
×
O
×
O
Preparation
×
×
O
×
O
B
Direct purging from absorber
Starting purging
×
O
O
×
O
Preparation
×
×
O
×
O
C
Manual purging from purging tank
Starting purging
O
×
O
×
O
D
Automatic purge of the purging tank
O
×
O
×
O
Note:
1. O: Open valve.
2. X: Closed valve.
Refrigerant refining method
Note:
Only use deionized water as the refrigerant in the chiller.
With an increase in the operation time of the chiller, some of the solution can mix in with the
refrigerant. Mixing the solution and the refrigerant lowers the refrigerating capacity. To prevent
this, refine the refrigerant periodically.
Refine the refrigerant according to the following procedure. The chiller must be operating to refine
refrigerant.
149
YHAU-C Single Effect Steam-Fired Absorption Chiller
Summary of Contents for York YHAU-C
Page 2: ......
Page 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Page 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Page 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Page 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Page 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Page 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...