JOHNSON CONTROLS
44
FORM 150.72-NM1 (1020)
Installation
FIG. 9 – SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT SWITCH
OR CIRCUIT BREAKER
SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED
DISCONNECT SWITCH OR CIRCUIT BREAKER
Electrical Notes and Legend located on page 68.
It is possible that multiple sources
of power can be supplying the unit
power panel. To prevent serious
injury or death, the technician
should verify that NO LETHAL
VOLTAGES are present inside the
panel AFTER disconnecting power,
PRIOR to working on equipment.
The unit evaporator heater uses
120VAC. Disconnecting 120VAC
power from the unit, at or below freez
-
ing temperatures, can result in damage
to the evaporator and unit as a result
of the chilled liquid freezing.
Power Panel
Control Panel
Terminal Block,
NF Disconnect SW
or Circuit Breaker
1L1 1L2 1L3
G
R
D
MICROPANEL
Flow Switch
See electrical note 9
Power Panel
Control Panel
Power Panel
Control Panel
Terminal Block,
NF Disconnect SW
or Circuit Breaker
1L1 1L2 1L3
1L1 1L2 1L3
G
R
D
G
R
D
G
R
D
MICROPANEL
2
L
XTBC2
XTBC1
13
14
Flow Switch
See electrical note 9
Field
Provided
Unit Power
Supply
Field Provided 120-1-60
Micropanel Power Supply if
Control Transformer not supplied.
Field supplied control power wiring
must be run in separate grounded
conduit. Never run control wiring
in the same conduit with power
wiring.
LD13141
Summary of Contents for YORK Tempo YLAA Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Page 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Page 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Page 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Page 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Page 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Page 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Page 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Page 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Page 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Page 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Page 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...