FORM 150.72-NM1 (1020)
169
JOHNSON CONTROLS
9
CHECKING INPUTS AND OUTPUTS
Digital Inputs
Refer to the unit wiring diagram.
All digital inputs are
connected to J13-1 of the I/O board. The term “digital”
refers to two states – either on or off. As an example,
when the flow switch is closed, 30V
DC will be applied
to J13, pin 5 (J13-5) of the I/O board. If the flow switch
is open, 0VDC will then be present at J13-5.
Pin 1 of J13 is an
unregulated
30VDC
source
used to
supply the DC voltage to the various user contacts, unit
switch, flow switch, etc. This
DC source is factory wired
to XTBC1, terminal 13. Any switch or contact used as a
digital input would be connected to this terminal, with
the other end connecting to its respective digital input on
the microboard. Any time a switch or contact is closed,
30VDC would be applied to that particular digital input.
Any time a switch or contact is open, 0VDC would be
applied to that particular digital input.
Typically, voltages of 24 – 36VDC could be measured
for the DC voltage on the digital inputs. This voltage
is in reference to ground. The unit case should be
sufficient as a reference point when measuring digital
input voltages.
Analog Inputs – Temperature
Refer to the unit wiring diagram.
Temperature inputs are
connected to the microboard on plug J6. These
analog
inputs represent varying DC signals corresponding to
varying temperatures. All voltages are in reference to
the unit case (ground). Following are the connections
for the temperature sensing inputs:
Outside Air Sensor
J6-6 = +5VDC regulated supply to sensor.
J6-9 = VDC input signal to the microboard.
See Table 24 for voltage readings that corre-
spond to specific outdoor temperatures.
J6-3 = drain (shield connection = 0VDC) Return
TABLE 24 – OUTDOOR AIR SENSOR
TEMPERATURE/VOLTAGE/
CORRELATION
TEMP °F
VOLTAGE
(Signal Input
to Return)
TEMP °C
0
0.7
-18
5
0.8
-15
10
0.9
-12
15
1.0
-9
20
1.1
-7
25
1.2
-4
30
1.4
-1
35
1.5
2
40
1.7
4
45
1.8
7
50
2.0
10
55
2.2
13
60
2.3
16
65
2.5
18
70
2.6
21
75
2.8
24
80
2.9
27
85
3.1
29
90
3.2
32
95
3.4
35
100
3.5
38
105
3.6
41
110
3.7
43
115
3.8
46
120
3.9
49
125
4.0
52
130
4.1
54
Summary of Contents for YORK Tempo YLAA Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Page 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Page 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Page 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Page 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Page 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Page 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Page 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Page 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Page 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Page 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Page 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...