Unit Operation
TABLE 18 – YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY
(5 OR 6 FANS PER SYSTEM)
FAN
STAGE
ON*
OFF**
IPUII I/O OUTPUT
FAN CONTACTOR
FAN #
SYS 1
SYS 2
SYS 1
SYS 2
SYS 1
SYS 2
1
DP >
PROGRAMMED
FAN CONTROL
ON PRESSURE
DP <
PROGRAMMED
FAN CONTROL
ON PRESSURE
MINUS
PROGRAMMED
DIFFERENTIAL
PRESSURE
TB7-8
TB10-8
1-KF1
2-KF1
1-MF1
2-MF1
2
DP >
PROGRAMMED
FAN CONTROL
ON PRESSURE &
FAN STAGE 1 IS
ENERGIZED
DP <
PROGRAMMED
FAN CONTROL
ON PRESSURE
MINUS
PROGRAMMED
DIFFERENTIAL
PRESSURE &
FAN STAGE 1
IS ENERGIZED
TB7-8 &
TB7-9
TB10-8 &
TB10-9
1-KF1 &
1-KF2
2-KF1 &
2-KF2
1-MF1 &
1-MF2 &
1-MF3
2-MF1 &
2-MF2 &
2-MF3
3
DP >
PROGRAMMED
FAN CONTROL
ON PRESSURE
AND FAN
STAGES 1 & 2
ARE ENERGIZED
DP <
PROGRAMMED
FAN CONTROL
ON PRESSURE
MINUS
PROGRAMMED
DIFFERENTIAL
PRESSURE &
FAN STAGES
1 & 2 ARE
ENERGIZED
TB7-8 &
TB7-9 &
TB7-10
TB10-8 &
TB10-9 &
TB10-10
1-KF1 &
1-KF2 &
1-KF3
2-KF1 &
2-KF2 &
2-KF3
5 FAN:
1-MF1 &
1-MF2 &
1-MF3 &
1-MF4 &
1-MF5
6 FAN:
1-MF1 &
1-MF2 &
1-MF3 &
1-MF4 &
1-MF5&
1-MF6
5 FAN:
1-MF1 &
1-MF2 &
1-MF3 &
1-MF4 &
1-MF5
* When a fan stage is turned on, the pressure for the next stage is increased 20 PSIG and ramped back to the programmed on pressure over
the next 20 seconds.
** When a fan stage is turned off (Programmed ON pressure minus the differential), the OFF pressure for the next stage is decreased 20 PSIG
and ramped back to the programmed OFF pressure minus the differential.
The time delay (fan delay timer) be
-
tween turning fan stages on and off is
fixed at 5 seconds.
Summary of Contents for YORK Tempo YLAA Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Page 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Page 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Page 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Page 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Page 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Page 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Page 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Page 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Page 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Page 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Page 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...