FORM 150.72-NM1 (1020)
127
JOHNSON CONTROLS
7
STATUS KEY
Unit Status
Pressing the STATUS key will enable the operator to
determine current chiller operating status. The messages
displayed will include running status, cooling demand,
fault status, external cycling device status. The display
will be a single message relating to the highest priority
message as determined by the microprocessor. Status
messages fall into the categories of General Status and
Fault Status.
The following General, Safety, and Warning messages
are displayed when the STATUS key is pressed.
Following each displayed message is an explanation
pertaining to that particular message.
General Status Messages
In the case of messages which apply to individual
systems, SYS 1 and SYS 2 messages will both be
displayed and may be different. In the case of single
system units, all SYS 2 messages will be blank.
This message informs the operator that the UNIT switch
on the control panel is in the OFF position which will
not allow the unit to run.
The REMOTE CONTROLLED SHUTDOWN message
indicates that either an ISN system or RCC has turned
the unit “OFF”, not allowing it to run.
U N I T S W I T C H O F F
S H
U T D
O
W
N
R E M O T E C O N T R O L L E D
S H
U T D
O
W
N
The DAILY SCHEDULE SHUTDOWN message
indicates that the daily/holiday schedule programmed
is keeping the unit from running.
REMOTE STOP NO RUN PERM shows that a remote
start/stop contact is open in series with the flow switch.
These contacts are connected to Terminals 51 and 13 of
XTBC1. A 3-second delay is built into the software to
prevent nuisance shutdowns due to erroneous signals
on the run permissive input.
FLOW SWITCH OPEN indicates the flow switch
contacts connected to Terminals 13 and 14 of XTBC1
are open. A 3-second delay is built into software to
prevent nuisance shutdowns due to erroneous signals
from the flow switch.
SYS SWITCH OFF tells that the system switch under
OPTIONS is turned “OFF”. The system will not be
allowed to run until the switch is turned back on.
D A I L Y S C H E D U L E
S H
U T D
O
W
N
R E M O T E S T O P
N O R U N P E R M
F L O W S W I T C H
O P E N
S Y S 1 S Y S S W I T C H O F F
S Y S 2 S Y S S W I T C H O F F
00066VIP
Summary of Contents for YORK Tempo YLAA Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Page 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Page 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Page 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Page 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Page 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Page 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Page 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Page 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Page 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Page 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Page 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...