JOHNSON CONTROLS
126
FORM 150.72-NM1 (1020)
Unit Controls
The on-board power supply converts 24 VAC from
75 VA, 120/24 VAC 50/60Hz UL listed class 2 power
transformer to +12V, +5V and +3.3V using switching
and linear voltage regulators located on the I/O and IPU
II boards. These voltages are used to operate integrated
circuitry on the board. The 40 character display and
unit sensors (transducers and temp sensors) are supplied
power for the microprocessor board +5V supply. 24V
AC is rectified, but not regulated, to provide unregulated
+30 VDC to supply all of the digital inputs.
The IPU II board contains one green “Power” LED
to indicate that the board is powered up and one red
“Status” LED to indicate by blinking that the processor
is operating.
The I/O board contains one green “Power” LED to
indicate that the board is powered up and one red
“Status” LED to indicate by blinking that the processor
is operating. The I/O board also contains two sets of
Receiver/Transmit LED’s, one for each available serial
communication port. The receive LED’s are green, and
the Transmit LED’s are red.
A jumper on the I/O board selects 4 to 20mA or 0 to 10
VDC as the input type on the remote temperature reset
analog input.
TRANSFORMER
A 75 VA, 120/24VAC 50/60Hz transformer is provided
to supply power to the Microprocessor Board, which in
turn rectifies, filters, and regulates as necessary to supply
power to the display, sensors, and transducers.
DISPLAY
The 40 Character Display (2 lines of 20 characters)
is a liquid crystal display used for displaying system
parameters and operator messages.
The display in conjunction with the keypad, allows the
operator to display system operating parameters as well
as access programmed information already in memory.
The display has a lighted background for night viewing
and for viewing in direct sunlight.
When a key is pressed, such as the OPER DATA key,
system parameters will be displayed and will remain
on the display until another key is pressed. The system
parameters can be scrolled with the use of the ↑ (
UP)
and ↓ (
DOWN) arrow keys. The display will update all
information at a rate of about 1 a second.
Display Messages may show characters indicating
“greater than” (>) or “less than” (<). These characters
indicate the actual values are greater than or less than
the limit values which are being displayed.
KEYPAD
The 12 button non-tactile keypad allows the user
to retrieve vitals system parameters such as system
pressures, temperatures, compressor running times
and starts, option information on the chiller, and
system setpoints. This data is useful for monitoring
chiller operation, diagnosing potential problems,
troubleshooting, and commissioning the chiller.
It is essential the user become familiar with the use of the
keypad and display. This will allow the user to make full
use of the capabilities and diagnostic
features available.
UNIT SWITCH
A unit ON/OFF switch is just underneath the keypad.
This switch allows the operator to turn the entire unit
“OFF” if desired. The switch must be placed in the “ON”
position for the chiller to operate.
BATTERY BACK-UP
The IPU II contains a Real Time Clock integrated circuit
chip with an internal battery backup. The purpose of
this battery backup is to assure any programmed values
(setpoints, clock, cutouts, etc.) are not lost during a
power failure regardless of the time involved in a power
cut or shutdown period.
PROGRAMMING # OF COMPRESSORS
The total number of compressors is programmable under
the PROGRAM key. Dual (2) system chillers can have
4, 5, or 6 compressors.
Summary of Contents for YORK Tempo YLAA Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Page 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Page 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Page 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Page 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Page 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Page 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Page 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Page 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Page 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Page 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Page 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...