1133394-YIM-A-1014
56
Johnson Controls Unitary Products
SIMPLICITY™ SE (SMART EQUIPMENT) FIRMWARE VE RSION 3. BASIC UNIT CONTROL BOARD NAVIGATION
EXAMPLES:
The following document details the navigation and viewing of
the LCD display screen equipped as a standard item on the
Simplicity SE control installed within various commercial UPG
packaged and split system equipment. The following
information provides a step-by-step demonstration on how to
navigate the basic status menu and how to change basic
configuration settings. The basic navigation steps outlined in
this short demonstration applies to most menus within the
Simplicity SE control.
Understanding the Local LCD
After you apply power to your Rooftop Unit (RTU), a start-up countdown begins
on the Unit Control Board (UCB) LCD. When the controller is ready, the screen is
blank because no faults are present. Use the joystick and the two push buttons
below the LCD, to navigate through the menus.
Joy
S
tick Dow
n
ENTER
CANCEL
JOY +
-
C PWR
7
7
7 7
T
>Status
Alarms
Step 1
- After the start-up countdown is
FRPSOHWHWKH¿UVWVFUHHQGLVSOD\HGLVWKH
“Status & Alarms” screen. When the cursor is
on the top “Status” line hit the “ENTER” button.
This action steps the LCD display into the
status mode. Hit “ENTER” to view the status
menu.
Press Enter
Step 2
- Scroll down to “DVent-
Mode”. This is the demand ventila-
tion mode.
ENTER
CANCEL
JOY +
-
C PWR
7
7
7 7
>DVent-Mode
OprST
Press Enter
Step 3 -
When the cursor is on the “DVent-Mode”
hit “ENTER” to view the status of this mode. In
this case a CO2 sensor is not installed, thus
Demand Ventilation or DVent is disabled.
ENTER
CANCEL
JOY +
-
C PWR
7
7
7 7
DVent-Mode
Disabled
Push Cancel
Step 4 -
To exit out of the
“DVent-Mode status screen
push “Cancel”. The screen
returns to that shown below.
ENTER
CANCEL
JOY +
-
C PWR
7
7
7 7
>DVent-Mode
OprST
Joy S
tick Dow
n
T
Step 5-
By pushing the joystick down, the cursor toggles to OprST
(Operating Space Temp).
Press Enter
ENTER
CANCEL
JOY +
-
C PWR
7
7
7 7
DVent-Mode
>OprST
ENTER
CANCEL
JOY +
-
C PWR
7
7
7 7
OprST
70.5 F
T
Joy
S
tick Dow
n
Step 6-
By pushing “ENTER” the actual OprST (Operating Space Temp) appears. Pushing
the joystick down scrolls through SAT, RAT, OAT and other available sensor readings.
ENTER
CANCEL
JOY +
-
C PWR
7
7
7 7
SAT
70.5 F
ENTER
CANCEL
JOY +
-
C PWR
7
7
7 7
RAT
70.5 F
ENTER
CANCEL
JOY +
-
C PWR
7
7
7 7
OprOAT
70.5 F
Press the “Cancel” button to exit each menu level. Repeatedly pressing
³&DQFHO´UHWXUQVWKHPHQXWRWKH¿UVW³6WDWXV$ODUPV´VFUHHQ
T
T
T