APPENDIX B - PROGRAMMABLE SETPOINT VALUES
TABLE 13 -
PROGRAMMABLE SETPOINT VALUES
EVAPORATOR SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Leaving Chilled Liquid Temperature - Setpoint
Operator
38.0 °F - Water
36.0 °F - Sm Frz
10.0 °F - Brine
70.0 °F
45.0 °F
Local Leaving Chilled Liquid Temperature - Range
Operator
10.0 °F
20.0 °F
10.0 °F
LCHLT Cycling Offset - Shutdown
Operator
1.0°F
Varies with
LCHLT setpoint
and chilled liquid
type.
4.0 °F or highest
allowed value,
whichever is
lower.
LCHLT Cycling Offset - Restart
Operator
0.0 °F
Varies with
LCHLT setpoint
and chilled liquid
type.
0.0 °F
Brine Low Evaporator Cutout
Service
0.0 PSIA
12.5 PSIA
12.5 PSIA
Sensitivity
Service
10 %
200 %
100 %
Smart Freeze
Service
Off
On
Off
Refrigerant (Sensor)
Service
Disabled
Enabled
Disabled
LOAD RATE SCREEN (EVAPORATOR SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Load Rate
Service
0.38 °F / Min, 0.75°F / Min, 1.13 °F /
Min, 1.50 °F / Min, 2.25 °F / Min, 3.00°F
/ Min, 5.25°F / Min, 10.50 °F / Min
0.38 °F / Min
Sensitivity
Service
10%
200%
100%
Pulse Time
Service
0.1 Secs
10.0 Secs
0.1 Secs
Pulse Period
Service
0.0 Secs
10.0 Secs
2.0 Secs
CONDENSER SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
High Pressure Warning Threshold
Service
14.0 PSIA
28.8 PSIA
28.8 PSIA
Drop Leg (Sensor)
Service
Disabled
Enabled
Disabled
Refrigerant (Sensor)
Service
Disabled
Enabled
Disabled
Purge Type
Service
TurboGuard, SkyGuard Local,
SkyGuard Remote
SkyGuard
Remote
PURGE SCREEN (CONDENSER SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
High Efficiency Purge System
Service
Disabled
Enabled
Disabled
Maximum Purges / Hour
Operator
10
30
20
Maximum Purges / Hour
Service
1
30
20
Summary of Contents for YORK OPTIVIEW CONTROL CENTER
Page 12: ...JOHNSON CONTROLS 12 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 118: ...JOHNSON CONTROLS 118 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 140: ...JOHNSON CONTROLS 140 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...