Y99AB-4 BASO® Test Kit

MILLIAMPS

MILLIVOLTS

20

0

10

10

0

300

DC MILLIVOLTS

PENN-BASO CONTROLS

500

700

900

30

40

50

MILLIAMPS

0-500

0-1000  0-50

MILLIVOLTS

JOHNSON CONTROLS, INC

WATERTOWN, WI.,  U.S.A

ADJUST

TCN10-4

Thermocouple Nut

31543-3

Thermocouple

Terminal Nut

40073-4

Lead Nut

64119-1D

Adapter Assembly

44549-4

Lead Assembly

44549-7

Lead Assembly

Figure 1: Y99AB-4 Test Kit

Description

The Y99AB-4 Test Kit combines four test functions
to enable service contractors to test BASO® controls
and thermocouples in the field. These four functions
are:

 

Millivoltmeter

 with 0 to 50 and 0 to 1000 ranges

for checking the open and closed circuit
millivoltage of thermocouple leads.

 

Performance Tester

 with a source of power for

holding open BASO power units while taking
open circuit millivolt readings of the
thermocouple when the main burner is in
operation.

 

Milliammeter

 with a 0 to 500 (50 on scale)

range for checking the current dropout range of
BASO power unit assemblies. (There are
10 milliamperes for each division on the dial.)

 

Continuity Tester

 for detecting a broken or

open circuit.

Definitions

Automatic Pilot

 - A device employed with gas burning

equipment, which automatically shuts off the gas supply
to the burner being served by either direct or indirect
means when the pilot flame is extinguished. The pilot
burner may or may not be constructed integrally with the
device.

Closed Circuit

 - Millivoltage measured with the BASO

control attached to the thermocouple.

Couple Lead

 - The thermocouple, current carrying

conductors, and attaching nut.

Dropout

 - The point, defined by a millivolt or milliampere

reading, at which the electromagnet releases the
armature.

Milliampere

 - One thousandth of an ampere.

Abbreviation mA used to check BASO control dropout.

Millivolt

 - One thousandth of a volt. Abbreviation mV

used to measure thermocouple output.

Open Circuit

 - Millivoltage measured without the BASO

control attached to the thermocouple.

Power Unit

 - Electromagnet unit that is internally

connected to the seat of the gas valve and cuts off the
gas when pilot flame fails. Also called a power unit
assembly or hood.

Reset Button

 - The button that is manually depressed to

place the BASO control in operation.

Thermocouple

 - The pair of dissimilar metallic elements

joined to produce a millivoltage when the junctions are at
different temperatures.

Summary of Contents for Y99AB-4

Page 1: ...res for each division on the dial Continuity Tester for detecting a broken or open circuit Definitions Automatic Pilot A device employed with gas burning equipment which automatically shuts off the gas supply to the burner being served by either direct or indirect means when the pilot flame is extinguished The pilot burner may or may not be constructed integrally with the device Closed Circuit Mil...

Page 2: ... thermocouple operated gas valve electrically operated gas valve and safety shutoff device connection diagrams Perform the following procedure for taking open circuit millivolt readings 1 Shut off the gas supply at the main manual shutoff valve 2 Disconnect the thermocouple from the BASO control 3 Attach the test cable lead 44549 8 to the thermocouple Connect the red clip to the copper tubing of t...

Page 3: ...p to the copper tubing of the adapter assembly and the black clip to the control end of the adapter assembly see Figure 5 3 Set the slide switch on the meter to the 0 50 or 0 1000 position 4 Reestablish pilot flame 5 The millivolt reading should agree with the values listed in Table 1 with a normal pilot flame see Figure 3 Note When taking a fixed load millivolt reading on a junction block thermoc...

Page 4: ... The milliampere reading at the moment of release is the dropout point of the BASO power unit Take two more readings by the same process and average the readings The milliampere dropout point must lie within the high and low range listed in Table 2 7 Pilot and main burner should extinguish within a few seconds If flames do not extinguish refer to the Troubleshooting section 44549 8 H17 Gas Valve R...

Page 5: ...llowing procedure for closed circuit testing 1 Disconnect the thermocouple from the BASO control 2 Attach the adapter assembly 64119 1D to the control and thermocouple 3 Remove the shorting jumper clip from the adapter assembly 4 Set the slide switch on the meter to the 0 50 position 5 Attach the test cable lead 44549 8 Connect the red clip to the copper tubing of the thermocouple and the black cl...

Page 6: ... 44549 8 Figure 8 Typical Thermocouple operated Gas Valve Connection Diagram Power Source Thermostat Transformer 44549 7 44549 8 BASO Magnetic Operator BASO Power Unit Reset Button B Valve Shutoff Valve Pilot Burner Gas Line Thermocouple Lead Red Black Figure 9 Typical Electrically operated Gas Valve Connection Diagram ...

Page 7: ...it Application Note 7 Transformer Shutoff Valve Pilot Burner Gas Line 44549 7 Black Red 44549 8 B Valve L Series Control Power Source Thermostat Thermocouple Lead Figure 10 Typical Safety Shutoff Device Connection Diagram ...

Page 8: ...r burning manual valve if included turned to the On position thermostat calling for heat Main burner does not come on Defective operator Check for operator input voltage If present replace the valve If not check voltage source Shorted thermostat circuit Perform the Continuity Testing procedure Thermostat not calling for heat or turned down manual valve if included in the On position Main burner do...

Reviews: