Johnson Controls VRF Smart Gateway Installation Instructions Manual Download Page 11

Table 4: VRF Smart Gateway

TYPE 1

TYPE 1 or TYPE 2
Action

Pollution Degree 2

External Pollution
Situation

330 V

Rated Impulse Voltage

100º C (212º F)

Ball Pressure
Temperature

United States

UL Listed File E107041, ANSI/UL 60730-1, UL Standard for Automatic Electrical Controls

for Household and Similar Use.

Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed Transmitters

Transmitter FCC Identification: OEJ-MAPWIFI

FCC Compliant to CFR 47, Part 15, Subpart B, Class A

Compliance

Canada:

cUL Listed File E107041, CAN/CSA-E60730-1, Canadian Standard for Automatic Electrical

Controls for Household and Similar Use

Industry Canada IC: 279A-MAPWIFI

IC: RSS-210, ICES-003

Europe:

CE Mark – Johnson Controls declares that this product is in compliance with the essential

requirements and other relevant provisions of the RED Directive, the EMC Directive, and the Low
Voltage Directive (LVD).

CE Emission:

EN61000-6-3; Generic standards for residential, commercial, and light-industrial

environments. ETSI EN 301 489-1, ETSI EN301 489-3 (Class 2), IEC 60730-1/ EN 60730-1

1

Last digit (

x

) represents non-US country requirements.

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for
damages resulting from misapplication or misuse of its products.

BACnet Points

The following table lists the indoor units (IDUs) as exposed by the VRF Smart Gateway.

Table 5: VRF BACnet Points for Indoor Units

Contents of Information

Object Type

Object Description

Object Name

BACnet
Instance
Number

0~255

Value

AI

Indoor Unit Capacity Code

UNIT-CAP

4

Enable

Shutdown

Setting

BO

Unit Enable Mode

UNITEN-MODE

5

Auto

Heat

Fan

Dry

Cool

Setting

MO

Command System Mode

SYSTEM-MODE

6

True

False

Status

BI

Heat/Cool Required

HtClg-REQ

7

Auto

High

Medium

Low

Setting

MO

Commanded Supply Fan
Speed

SF-SPEED-C

8

0.0~100.0%

Value

AI

Expansion Valve Position

EXPV-%

9

-50~99°C / -58~210°F

Value

AI

Liquid Pipe Temperature

LIQ-PIPE-T

10

-50~99°C / -58~210°F

Value

AI

Gas Pipe Temperature

GAS-PIPE-T

11

-50~99°C / -58~210°F

Value

AI

Return Air Temperature

RA-T

12

11

VRF Smart Gateway Installation Instructions

Summary of Contents for VRF Smart Gateway

Page 1: ...to be up to 30 m 100 ft line of sight away Power must be supplied using the provided external power supply North American Emissions Compliance United States This equipment has been tested and found to...

Page 2: ...unit upside down which puts the labels upside down Location Considerations Observe the following guidelines when mounting a VRF Smart Gateway Mount the VRF Smart Gateway in areas free of corrosive vap...

Page 3: ...ace to which the unit is mounted The screw holes on the VRF Smart Gateway can accommodate M3 5 and 6 screws For information on location considerations for maximizing signal strength see the Mounting s...

Page 4: ...h you are connecting Wiring the H Link Network To wire the H Link Network of the VRF Smart Gateway Connect the two H Link cable wires to the left terminals indicated in the following figure If the VRF...

Page 5: ...ne disconnection or isolation may be required to completely de energize equipment Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury o...

Page 6: ...overed VRF devices A software update may be available for your device Visit VRFPro com or contact your nearest Johnson Controls representative for the latest version Refer to the VRF Smart Gateway Use...

Page 7: ...Fi and Ethernet Settings 1 Press and hold the reset button for 6 seconds After 2 seconds the Fault LED displays Slow Flicker behavior This changes to Fast Flicker behavior after an additional 4 second...

Page 8: ...sion On Steady Green Ethernet Off No Wi Fi signal or no devices currently connected over Wi Fi Wi Fi strength is indicated by the number of LEDs that are lit with one lit LED indicating weak wireless...

Page 9: ...the corrupted key or certificate to be saved The server detects the error and returns the Error Saving SSL Settings message While this correctly prevents the bad key or certificate from being used it...

Page 10: ...d Access Pre Shared Key mode Temporal Key Integrity Protocol WPA2 EAP PEAP WPA2 EAP TLS Wireless Security One H Link port 4 pin port Network and Serial Interfaces 145 4 x 85 4 x 40 1 mm 5 72 x 3 36 x...

Page 11: ...1 ETSI EN301 489 3 Class 2 IEC 60730 1 EN 60730 1 1 Last digit x represents non US country requirements The performance specifications are nominal and conform to acceptable industry standard For appli...

Page 12: ...Fan Dry Cool Status MI Actual System Mode SYSTEM S 25 High Medium Low Status MI Actual Supply Fan Speed SF SPD 26 50 99 C 58 210 F Value AI Zone Temperature ZN T 27 Dirty Clean Status BI Filter Statu...

Page 13: ...e INV HRS 11 0 655 350 Hours Value AI Compressor 2 Runtime COMP HRS 12 0 255 Hz Value AI Inverter Compressor Frequency INV FREQ 13 0 65 535 Hz Value AI Total Frequency TOTAL FREQ 14 0 100 Value AI Out...

Page 14: ...s Enum Value Thermo off 1 Pump down 2 SW on start 3 Thermo on start 4 After defrost 5 Start control 1 6 Start control 2 7 Normal 8 Oil return 9 Defrost ready 1 10 Defrost ready 2 11 Differential press...

Page 15: ...f synchronism 21 Na4 22 Na5 23 Normal acceleration 24 Normal deceleration 25 Constant speed 26 Overload after the acceleration 27 Overload after the deceleration 28 Overload after constant speed 29 Po...

Page 16: ...NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY Building Technologies Solutio...

Reviews: