Johnson Controls VMA1930 Installation Manual Download Page 4

Mounting

Observe the following guidelines when mounting a

VMA:

Note: 

When the air supply to the VAV box

is below 10°C (50°F), make sure that any

condensation on the VAV box, particularly on

the damper shaft, does not enter the VMA

• Ensure that the mounting surface can support

the controller and any user-supplied enclosure.

electronics. Mount the controller vertically above

the damper shaft to allow any shaft condensation

to fall away from the controller. Additional

measures may be required in some installations.

• Mount the controller on a hard, even surface

whenever possible.

• Use shims or washers to mount the controller

securely and evenly on the mounting surface.

• Mount the controller in an area free of corrosive

vapors that matches the ambient conditions

specified in the 

Technical specifications

 section.

• Provide sufficient space around the controller

for cable and wire connections and adequate

ventilation through the controller (at least 50 mm

[2 in.] on the top, bottom, sides, and front of the

controllers).

• Mount the VMA vertically above the damper shaft

to allow any shaft condensation to fall away from

the VMA.
Do not mount the controller in areas where

electromagnetic emissions from other

devices or wiring can interfere with controller

communication.

• Avoid mounting the controller on surfaces with

excessive vibration.

On panel or enclosure mount applications, observe

these additional guidelines:
• Do not install the controller in an airtight

enclosure.

• Mount the controller so that the enclosure walls

do not obstruct cover removal or ventilation

through the controller.

• Mount the controller so that the power

transformer and other devices do not radiate

excessive heat to the controller.

To mount the controllers, complete the following

steps:

1.  Set all the switches on the field controller to

their known settings.

2.  Place the controller in the proper mounting

position on the damper shaft so that the wiring

connections are easily accessible. Make sure

the controller base is parallel to the VAV box

(perpendicular to the damper shaft). If needed,

use a spacer to offset tipping of the controller

caused by the shaft bushings.

Note: 

Use the alignment marks to center

the captive spacer to ensure sufficient

movement in either direction.

3.  Secure the self-drilling No. 10 screw through

the captive spacer with a power screwdriver

and 100 mm (4 in.) extension socket. Otherwise,

use a punch to mark the position of the

shoulder washer, and then drill a hole into the

VAV box using a 3.5 mm (9/64 in.) drill bit. Insert

the mounting screw and tighten against the

spacer.

Important: 

Do not overtighten the screw,

or the threads may strip. If mounting to

the VAV box, make sure the screws do not

interfere with damper blade movement.

4.  Locate the damper position using the typical

marking on the end of the damper shaft as

shown in the following figure.

Figure  2: Typical Damper End Shaft Icons

5.  Note the direction, clockwise (CW) or

counterclockwise (CCW), required to close the

damper. Grasp the damper shaft firmly with

pliers, and either manually close the damper for

90° boxes or manually open the damper for 45°

or 60° boxes.

VMA1930 VAV Controller Installation Guide

4

Summary of Contents for VMA1930

Page 1: ...ence when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction m...

Page 2: ...Table 3 5 Dual Port Fitting 6 Manual Override Button see Mounting for information about using manual override Button 7 Controller Coupler see Mounting for information about using the controller couple...

Page 3: ...0mA Analog Input Resistive Mode 0 2k ohm RTD 1k NI Johnson Controls 1k PT A998 SI NTC 10k Type L 2 252k Type 2 Binary Input Dry Contact Maintained Mode 3 Binary Output BO 24 VAC Triac 3 Configurable O...

Page 4: ...ller so that the enclosure walls do not obstruct cover removal or ventilation through the controller Mount the controller so that the power transformer and other devices do not radiate excessive heat...

Page 5: ...ing an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to 10 5 to 11 5 N m 95 to 105 lb in 9 Skip this step if you are installing the VMA1626 model Loop the pneumatic tubing supplied by fi...

Page 6: ...port Benefits of daisy chained networks are that they require less physical wiring and new devices can be added easily to the network In a star network each VMA1930 controller is connected by Ethernet...

Page 7: ...inal block is a gray removable 2 terminal plug that fits into a board mounted jack on the upper left of the VMA controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM te...

Page 8: ...dress See Setting the controller number Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the...

Page 9: ...1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 4...

Page 10: ...s Table 4 Cable length guidelines Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 2...

Page 11: ...Communications COM SA Bus Signal Reference and 15 VDC Common SA BUS 2 2 POWER 15 VDC Supply Power for Devices on the SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended No...

Page 12: ...the figures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage...

Page 13: ...uator External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog...

Page 14: ...ing the controller Setting the controller number Each controller on a network must have a unique number on the subnet where it resides in order to identify it in the Controller Tool for uploading down...

Page 15: ...tions on the input and output terminals including the integrated DPT It assumes all Universal Inputs UIs are Nickel temperature sensors All Configurable Outputs COs are treated as Binary Outputs BOs w...

Page 16: ...uses to trip make sure that the power connections on theVMA1930 are not reversed The most common cause of this problem is when the 24 VAC power supply on the VMA1930 is reversed but not reversed on a...

Page 17: ...Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared between multiple pieces of equipment Configurable output analog mode is invalid 0 1...

Page 18: ...cm 30 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondar...

Page 19: ...een 001 and 999 Communications Bus Two Ethernet ports 10 100 Mbps 8 pin RJ 45 connector SA Bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VMA controller for netw...

Page 20: ...nced Application Controller B AAC based on the ANSI ASHRAE 135 2016 The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these sp...

Reviews: