LED status and states
Table 10: Status LEDs and description of LED states
LED label
LED color
Normal state
Descriptions of LED states
POWER
Green
On Steady
Off Steady = No power
On Steady = Power is supplied by primary voltage
FAULT
Red
Off Steady
Blink - 2 Hz = Download or startup in progress, not
ready for normal operation, SA Bus devices offline
(such as netsensors)
Rapid blink = SA Bus communications issue
Off Steady = No faults
On Steady = Device fault or no application loaded
FC BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data transmission (normal
communication)
Off Steady = No data transmission (auto baud in
progress)
On Steady = communication lost, waiting to join
communication ring
SA BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data transmission (normal
communication)
Off Steady = No data transmission (N/A - auto baud
not supported)
On Steady = Communication lost; waiting to join
communication ring
EOL
Amber
Off
On Steady = EOL is active
Off Steady = EOL is not active
Accessories
Table 11: VMA1617 and VMA1632 Controller Accessories (Order Separately)
Product code number
Description
IOM Series Controllers
Refer to the
Metasys
®
System Field Equipment Controllers and Related Products Product Bulletin
(LIT-12011042)
for a complete list of available IOM Series Controllers.
Mobile Access Portal (MAP) Gateway
Refer to the
Mobile Access Portal Gateway Catalog Page
(LIT-1900869) to identify the
appropriate product for your region.
MS-DIS1710-0
Local Controller Display
MS-BTCVTCBL-700
Cable Replacement Set for the MS-BTCVT-1 or the NS-ATV7003-0; includes One 1.5 m (5 ft)
Retractable Cable
Y64T15-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, Foot Mount, 72.2 cm (30
in.), Primary Leads and 76.2 cm (30 in.) Secondary Leads, Class 2
Y65A13-0
Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount (Y65AS), 20.32 cm (8
in.), Primary Leads and 76.2 cm (30 in.) Secondary Leads, Class 2
Y65T42-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Hub Mount (Y65SP+),
20.32 cm (8 in.), Primary Leads and Secondary Screw Terminals, Class 2
Y65T31-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount (Y65AR+),
20.32 cm (8 in.), Primary Leads and Secondary Screw Terminals, Class 2
AP-TBK1002-0
2-position Screw Terminal that plugs onto VMA Output Point Spade Lugs
AP-TBK1003-0
3-position Screw Terminal that plugs onto VMA Output Point Spade Lugs
AP-TBK4SA-0
Replacement MS/TP SA Bus Terminal, 4-Position Connector, Brown, Bulk Pack of 10
AP-TBK4FC-0
Replacement MS/TP FC Bus Terminal, 4-Position Connector, Blue, Bulk Pack of 10
AP-TBK2PW-0
Replacement Power Terminal, 2-Position Connector, Gray, Bulk Pack of 10
AS-CBLTSTAT-0
Cable adapter for connection to 8-pin TE-6700 Series sensors
VMA1617 and VMA1632 VAV Controllers Installation Guide
20