VFD67 Size A to D Getting Started Guide
45
Issue Number: 1
www.johnsoncontrols.com
Sa
fe
Rat
in
Me
ch
El
Ke
yp
Pa
ra
Qu
ick S
D
Pa
ra
Te
UL L
* The Enable/Reset terminal will not reset an O.Ld1 trip. Use the
Stop/Reset key.
** These trips cannot be reset for 10 seconds after they occur.
For a detailed description of how to reset the drive after it has tripped, contact the
supplier of the drive.
Table 8-1 DC bus voltages
Table 8-2 Alarm warnings/Display indications
Drive voltage rating
UV Trip
UV Reset
Braking level
OV trip
110V
175
215
*
390
415
200V
175
215
*
390
415
400V
330
425
*
780
830
* These are the absolute minimum DC voltages the drives can be supplied by.
NOTE
Display
Condition
Solution
OVL.d
I x t overload (I = current, t = time)
Reduce motor current (Load)
hot
Heatsink/IGBT temperature high
Reduce ambient temperature or reduce motor current
br.rS
Braking resistor overload
Contact the supplier of the drive
AC.Lt
Drive is in current limit
Contact the supplier of the drive
FAIL
Failed attempt to read stick
An attempt has been made to read the stick when the drive
was not disabled or tripped, or the stick is read-only.
If no action is taken when an alarm warning appears, the drive will trip on the appropriate fault
code.
NOTE