VFD67 Size A to D Getting Started Guide
27
Issue Number: 1
www.johnsoncontrols.com
Sa
fe
Rat
in
Me
ch
El
Ke
yp
P
Qu
ick S
D
P
Te
UL L
Figure 6-6 Pr 05 = E.Pot (binary control - increase / decrease speed)
When Pr
05
is set to E.Pot, the following parameters are made available for adjustment:
•
Pr
61
: Motorized pot up/down rate (s/100%)
•
Pr
62
: Motorized pot bipolar select (0 = unipolar, 1 = bipolar)
•
Pr
63
: Motorized pot mode: 0 = zero at power-up, 1 = last value at power-up,
2 = zero at power-up and only change when drive is running,
3 = last value at power-up and only change when drive is running.
Figure 6-7 Pr 05 = tor (torque mode)
0V
+10V reference output
+24V output
/Stop
Run
Jog
V
_
+
Analog output
(motor speed)
Digital output
(zero speed)
Down
Up
Not used
T1
T2
T3
T4
B1
B2
B3
B4
B5
B6
B7
0V
Remote current speed
reference input (A1)
+10V reference output
Torque reference
input (A2)
+24V output
/Stop
Run
Jog
Torque mode
select
Remote speed
reference input
V
_
+
10k
(2kmin)
Analog output
(motor speed)
Digital output
(zero speed)
T1
T2
T3
T4
B1
B2
B3
B4
B5
B6
B7