Johnson Controls VAV1717 Installation Manual Download Page 16

Note: 

Do not connect a wirelessly enabled

field controller to a wired FC Bus. Refer

to the 

ZFR1800 Series Wireless Field Bus

System Technical Bulletin (LIT-12011295)

 or

the 

ZFR1800 Series Wireless Field Bus System

Product Bulletin (LIT-12011336)

 for more

information about wireless applications.

3. Set a unique and sequential device address for

each of the controllers connected on the FC bus,

starting with device address 4. To ensure the best

bus performance, set sequential device addresses

with no gaps in the device address range (4, 5, 6, 7,

8, 9, and so on). The controllers do not need to be

physically connected on the bus in their numerical

device address order.

4. Write each controller’s device address on the white

label below the DIP switch block on the controller’s

cover.

Setting the EOL switch

About this task:  

Each field controller has an EOL switch that you can set

to ON (up) to set the field controller as a terminating

device on the bus. See 

Physical features

 for the EOL switch

location on the field controller. The default EOL switch

position is OFF (down). The amber EOL LED illuminates to

show that the EOL is active.

Figure 12: EOL ON position

Figure 13: EOL OFF position

To set the EOL switch on a field controller, complete the

following steps:

1. Determine the physical location of the controller on

the FC bus.

2. Determine if the controller must be set as a

terminating device on the bus.

Note: 

Refer to the 

MS/TP Communications Bus

Technical Bulletin (LIT-12011034)

 for detailed

information about EOL termination rules and

EOL switch settings on SA and FC buses.

3. If the controller is a terminating device on the FC

bus, set the EOL switch to ON. If the controller is

not a terminating device on the bus, set the EOL

switch to OFF.

Note: 

When the EOL switch is set to ON,

the EOL LED on the front of the controller is

illuminated.

Commissioning the controller

About this task:  

To commission the controller, use the Controller

Configuration Tool (CCT).

Note: 

To configure and commission controllers,

and to upgrade the firmware of the controllers to

the latest version, you must obtain the equipment

controller firmware package files for CCT. See the

product code MS-FCP-0, FX-FCP-0, or CH-FCP-0.

Beginning at CCT Release 13, you must order the

firmware package files separately, they are not

included with CCT. Obtain them from the software

licensing portal, and load and license them on the

computer or server that runs CCT. For additional

information about the firmware package files, refer

to the 

CCT Installation Instructions (LIT-12011529)

.

To commission the controller, complete the following

steps:

1. Connect the controller to the CCT using one of the

following methods:

- MAP4.2+/BACnet Router

Note: 

 This method is available for

Mobile Access Portal (MAP) Gateways

at version 4.2 or above.

- Bluetooth, using BTCVT

Note: 

The MAP Gateway serves as a

replacement for the BTCVT, which is

no longer available for purchase, but

continues to be supported. You can use

the Bluetooth connection to transfer to

the computer (upload) and commission

the controller, but you cannot use the

Bluetooth connection to transfer to the

device (download).

2. Download the control application to the controller

using the CCT. For more information, refer to the

Controller Tool Help (LIT-12011147)

 and 

Controller

Provisioning with Tools (LIT-12013247)

.

3. Commission the VAV Box.
4. Perform airflow balancing on the VAV box. Refer

to the 

VAV Balancing Tool and Network Sensors

Technical Bulletin (LIT-12011087)

.

5. Perform commission checkout procedures. Refer

to 

Controller Tool Help (LIT-12011147)

 and 

Controller

Provisioning with Tools (LIT-12013247)

.

VAV1717 and VAV1732 VAV Controllers Installation Guide

16

Summary of Contents for VAV1717

Page 1: ...ls provide a cost effective upgrade and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to th...

Page 2: ...Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input 0 ohm to 600k ohm qualified sensors 0 ohm to 2k ohm potentiometer RTD 1k Nickel 1k Platinum or A99B Si NTC 10k Type L 10k...

Page 3: ...Callout Description and references 15 SA bus modular port RJ 12 6 pin modular jack see SA bus port 16 LED status indicators see LED states VAV1717 and VAV1732 VAV Controllers Installation Guide 3...

Page 4: ...n see Mounting the controller 7 Controller coupler see Mounting the controller 8 Coupler bolt see Mounting the controller 9 Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input...

Page 5: ...ontroller Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller To mount the controller complete the following steps 1 Set all the switch...

Page 6: ...N Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Important Do not connect supply power to the controller before you finish wiring and b...

Page 7: ...on the SA bus 2 Daisy chained device on the SA bus 3 Cable shield connection 4 Connection to another device on the SA bus TSTAT port The TSTAT port on the face of the controller is an RJ 45 8 position...

Page 8: ...ontroller does not require an earth ground connection However when you need to ground the secondary of the 24 VAC transformer make only one ground connection near the transformer See the following fig...

Page 9: ...n for all Universal IN terminals Note All Universal ICOMn terminals are isolated from all other commons Same as Universal INn OUTn Binary Output 24 VAC Triac Internal Power Sources internal 24 VAC pow...

Page 10: ...BUS SA BUS RJ 12 6 position modular port that provides communications and 15 VDC power for the following devices NS and NSA Series network sensors MAP Gateway 4 2 or later Bluetooth Commissioning Conv...

Page 11: ...tput point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 137 m 450 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted...

Page 12: ...controller Table 9 Termination diagrams Type of field device Type of input or output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered U...

Page 13: ...External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low Externally Sourced CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Swi...

Page 14: ...th Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus...

Page 15: ...ock at the top of the controller see Physical features Device addresses 4 through 127 are the valid addresses for these controllers on an MS TP FC bus The DIP switch block has eight switches numbered...

Page 16: ...ch to OFF Note When the EOL switch is set to ON the EOL LED on the front of the controller is illuminated Commissioning the controller About this task To commission the controller use the Controller C...

Page 17: ...ries Fan On off heating water valve and variable speed series fan 8 On Off Series Fan Single speed series fan 8 Incr HW Reheat Var Speed Series Fan Incremental heating water valve and variable speed s...

Page 18: ...LED status indicator information for troubleshooting the controllers Note If you experience short circuits in the 24 VAC power supply causing protective devices such as breakers or fuses to trip make...

Page 19: ...nd COM Ensure that no short circuit occurs Note Some installations require the secondary of the transformer to be earth grounded If this is the case verify that the earth ground connection is valid an...

Page 20: ...BCPro Controller Firmware Package Files required for CCT TL MAP1810 0PA Portable MAP Gateway Australia China India Japan Malaysia New Zealand Singapore South Korea Thailand TL MAP1810 0PM Portable MAP...

Page 21: ...er TE730 Analog sensors with occupancy option TSTAT port NSA7000 Network sensors with occupancy option and RH display option NS7000 NS8000 Network sensors with occupancy option CO2 display option and...

Page 22: ...ded between the supervisory controller and the VAV controller SA bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VAV controller to network sensors and other senso...

Page 23: ...ns consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Repair information If the controller fails to oper...

Page 24: ...anty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license ope...

Reviews: