Series TY-FRL — 2.8, 5.6, and 8.0 K-factor  

Upright, Pendent, and Recessed Pendent Sprinklers 

Quick Response, Standard Coverage

Page 1 of 6 

AUGUST 2018 

TFP130

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

NOTICE

The Series TY-FRL Sprinklers 

described herein must be installed 

and maintained in compliance with 

this document, as well as with the 

applicable standards of the National 

Fire Protection Association, in addition 

to the standards of any other authori-

ties having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Numbers

TY1121    .  .  .  .  .  .  .  .  .  .  . Upright 2 .8K, 1/2 in . NPT
TY1221    .  .  .  .  .  .  .  .  .  .  .Pendent 2 .8K, 1/2 in . NPT
TY3121    .  .  .  .  .  .  .  .  .  .  . Upright 5 .6K, 1/2 in . NPT 
TY3221   .  .  .  .  .  .  .  .  .  .  .Pendent 5 .6K, 1/2 in . NPT 
TY4121    .  .  .  .  .  .  .  .  .  .  . Upright 8 .0K, 3/4 in . NPT 
TY4221    .  .  .  .  .  .  .  .  .  .  .Pendent 8 .0K, 3/4 in . NPT 

TY1121 is a redesignation for S1879 

and G8973.
TY1221 is a redesignation for S1880 

and G8971.
TY3121 is a redesignation for S1864 

and G8974.
TY3221 is a redesignation for S1865 

and G8972.
TY4121 is a redesignation for S1866 

and G8174.
TY4221 is a redesignation for S1867 

and G8172.

General 

Description

The TYCO Series TY-FRL, 2.8, 5.6, 

and 8.0 K-factor, Upright and Pendent 

Sprinklers described in this data sheet 

are quick response, standard coverage, 

solder type spray sprinklers designed 

for use in light and ordinary hazard 

commercial occupancies such as 

banks, hotels, shopping malls, schools, 

hospitals, etc.
The recessed version of the 2.8 and 5.6 

K-factor, Series TY-FRL Pendent Sprin-

kler, where applicable, is intended for 

use in areas with a finished ceiling. It 

uses a two-piece Style 20 (1/2 in. NPT) 

Recessed Escutcheon. The Recessed 

Escutcheon provides 1/4 in. (6,4 mm) 

of recessed adjustment or up to 1/2 in. 

(12,7 mm) of total adjustment from the 

flush pendent position. The adjustment 

provided by the Recessed Escutcheon 

reduces the accuracy to which the fixed 

pipe drops to the sprinklers must be 

cut.
An intermediate level version of the 

5.6 and 8.0 K-factor, Series TY-FRL 

Pendent Sprinkler can be obtained by 

utilizing the Series TY-FRL Pendent 

Sprinkler in combination with the Model 

S4 Shield.

Summary of Contents for tyco TY-FRL Series

Page 1: ...K 1 2 in NPT TY1221 Pendent 2 8K 1 2 in NPT TY3121 Upright 5 6K 1 2 in NPT TY3221 Pendent 5 6K 1 2 in NPT TY4121 Upright 8 0K 3 4 in NPT TY4221 Pendent 8 0K 3 4 in NPT TY1121 is a redesignation for S1879 and G8973 TY1221 is a redesignation for S1880 and G8971 TY3121 is a redesignation for S1864 and G8974 TY3221 is a redesignation for S1865 and G8972 TY4121 is a redesignation for S1866 and G8174 TY...

Page 2: ...GHT PENDENT CROSS SECTION RECESSED PENDENT 7 16 11 1 mm NOMINAL MAKE IN WRENCH FLANGES ESCUTCHEON PLATE SEATING SURFACE WRENCH AREA STYLE 20 RECESSED ESCUTCHEON Pipe thread connections per ISO 7 1 can be provided on special request Temperature rating is indicated on Deflector DEFLECTOR 2 7 8 73 0 mm DIA 5 6 9 3 2 4 7 8 1 1 2 Deflector Strut Frame Link Assembly Seal 9 Bushing Button 7 1 2 NPT 3 5 H...

Page 3: ...leak tight 1 2 in NPT sprinkler joint should be obtained with a torque of 7 to 14 lb ft 9 5 to 19 0 N m A leak tight 3 4 in NPT sprinkler joint should be obtained with a torque of 10 to 20 lb ft 13 4 to 26 8 N m Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler Do not attempt to make up for insuf ficient adjustment in the escutcheon plate by u...

Page 4: ...SH K TYPE TEMP RATING FRAME COLOR CODE NATURAL BRASS CHROME PLATED 2 8 1 2 in NPT PENDENT TY1221 165 F 74 C Unpainted 1 2 5 212 F 100 C White UPRIGHT TY1121 165 F 74 C Unpainted 212 F 100 C White RECESSED PENDENT TY1221 w Style 20 165 F 74 C Unpainted 212 F 100 C White 5 6 1 2 in NPT PENDENT TY3221 165 F 74 C Unpainted 1 2 3 4 5 212 F 100 C White 1 2 3 5 UPRIGHT TY3121 165 F 74 C Unpainted 1 2 3 4...

Page 5: ...ce with this document as well as with the applicable standards of the National Fire Protection Asso ciation e g NFPA 25 in addition to the standards of any other authorities having jurisdiction Contact the install ing contractor or product manufacturer with any questions It is recommended that automatic sprinkler systems be inspected tested and maintained by a qualified Inspec tion Service in acco...

Page 6: ... Thread Connections Specify Series TY FRL specify SIN specify K factor specify Upright Pendent or Recessed Pendent Sprin kler Quick Response specify temper ature rating specify type of finish P N specify from Table B Recessed Escutcheon Specify Style 20 Recessed Escutch eon with specify finish P N specify Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify W Type 9 Sprinkler Wrench P N 5...