Series TY-B — 5.6 K-factor 

Conventional (Old Style) Sprinklers 

Standard Response

Page 1 of 4 

AUGUST 2018 

TFP662

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Series TY-B, 5.6 K-fac-

tor, Conventional Sprinklers (TY365) 

described in this data sheet are stan-

dard response -standard coverage, 

decorative 5 mm glass bulb type 

spray sprinklers. These sprinklers are 

intended to be installed either pendent 

or upright, and in either position, they 

produce a spherical water discharge 

pattern with approximately 50% of 

the discharge directed upwards and 

approximately 50% of the discharge 

directed downwards.
Conventional sprinklers are generally 

used with Ordinary and Extra High 

Hazard Class Systems, as defined by 

the automatic sprinkler system installa-

tion rules of the country and authority 

having jurisdiction. The NFPA permits 

the use of “Old Style Sprinklers” where 

special construction features require a 

unique water distribution; for the pro-

tection of fur vaults; or, the replace-

ment of similar sprinklers that had been 

installed prior to 1955.

NOTICE

The TYCO Series TY-B 5.6 K-factor 

Conventional Sprinklers described 

herein must be installed and main-

tained in compliance with this docu-

ment, as well as with the applicable 

standards of the NATIONAL FIRE PRO-

TECTION ASSOCIATION, in addition to 

the standards of any other authorities 

having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number (SIN)

TY365 

TY3650 (LPCB Approved only)

Technical 

Data

Approvals

Refer to Table A

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K = 5.6 GPM/psi

1/2

 (80,6 LPM/bar

1/2

)

Temperature Ratings

135°F (57°C) 

155°F (68°C) 

175°F (79°C) 

200°F (93°C) 

286°F (141°C) 

360°F (182°C)

Finishes

Refer to Table B

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper

Sealing Assembly  . . . Stainless Steel w/TEFLON

Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass

Compression Screw . . . . . . . . . . . . . . . . .Bronze

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Operation

The glass bulb contains a fluid which 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the sprinkler to 

activate and water to flow.

Design 

Criteria

The TYCO Series TY-B, 5.6 K-factor, 

Conventional Sprinklers (TY365) are 

intended for fire protection systems 

designed in accordance with the stan-

dard installation rules recognized by the 

applicable Listing or Approval agency 

(e.g., UL Listing is based on NFPA 13 

requirements). The Series TY-B Con-

ventional Sprinklers are only for non-

recessed applications.

Summary of Contents for tyco TY-B Series

Page 1: ...sprinklers that had been installed prior to 1955 NOTICE The TYCO Series TY B 5 6 K factor Conventional Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the NATIONAL FIRE PRO TECTION ASSOCIATION in addition to the standards of any other authorities having jurisdiction Failure to do so may impair the performan...

Page 2: ...corrosion must be replaced Automatic sprinklers must never be painted plated coated or other wise altered after leaving the factory Modified sprinklers must be replaced Sprinklers that have been exposed to corrosive products of combustion but have not operated should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Ca...

Page 3: ...ils contact Johnson Controls Enschede Netherlands Tel 310530428 4444 Fax 31 53 428 3377 4 Where Polyester Coated Sprinklers are noted to be UL Listed the sprinklers are UL Listed as Corrosion Resistant Sprinklers Frame and Deflector only Sprinkler Wrench Specify W Type 6 Sprinkler Wrench P N 56 000 6 387 SPRINKLER FINISH 1 NATURAL BRASS 3 PURE WHITE RAL9010 POLYESTER 4 SIGNAL WHITE RAL9003 POLYEST...

Page 4: ...re Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2018 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Reviews: