Model LD — 11.2 K-factor
Large Drop Upright Sprinkler, Standard Response
Control Mode Specific Application
Page 1 of 4
AUGUST 2018
TFP335
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Model LD, 11.2 K-factor
Large Drop Upright Sprinkler, Stan-
dard Response Control Mode Specific
Application is a glass bulb type auto-
matic sprinkler. It is intended for use
with the National Fire Protection Asso-
ciation large drop sprinkler installation
criteria for the protection of high piled
storage. The LD Sprinkler can provide a
higher level of protection than standard
spray sprinklers and, in some cases,
can provide an economic advantage by
eliminating in-rack sprinklers.
NOTICE
The TYCO Model LD 11.2 K-factor,
Large Drop Upright Sprinkler described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number
Refer to Table A for sprinkler identifica-
tion number.
Technical
Data
Approvals
UL and C-UL Listed
NYC Approved under MEA 289-04-E
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Sealing Assembly . .Beryllium Nickel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . .Glass (5mm dia.)
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Additional Technical Data
Refer to Table A for additional techni-
cal data.
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The TYCO Model LD, 11.2 K-factor
Large Drop Upright Sprinkler, Stan-
dard Response Control Mode Specific
Application is only for use with National
Fire Protection Association “large drop
sprinkler” installation criteria.