Application Note 

 

Connecting an OSDP HID reader to a KT-400 controller 

Use this application note to wire a HID reader using OSDP protocol to a KT-400 controller 

and to configure the setup in EntraPass. 

Requirements 

  KT-400 Controller firmware 3.00.07 or higher 

  EntraPass Special, Corporate, or Global Edition 8.40 or later 

  HID Reader with OSDP communication 

  HID Reader Manager mobile application 

  Mobile device with Bluetooth 

Note

: Kantech have implemented Open Supervised Device Protocol (OSDP) 2.2. OSDP is 

an access control communications standard developed by the Security Industry Association 

(SIA). For more information about the protocol, refer to 

https://www.securityindustry.org/industry-standards/open-supervised-device-protocol/

. 

Wiring the HID reader to the KT-400 controller 

Use the RS-485 COM (COM2) port for OSDP communication.

  

 

1.  Disconnect the power to the KT-400 controller. 
2.  Connect the reader’s red wire to the +12VDC. 
3.  Connect the reader’s black wire to the earth ground GND. 
4.  Connect the reader’s white wire to the COM 485 +. 
5.  Connect the reader’s green wire to the COM 485 -. 

For more information about installing and wiring the KT-400 controller, refer to the 

KT-400 

Four-Door Controller Installation Guide

Configuring the card reader using the HID mobile app 

Use the HID Reader Manager mobile application to set up the HID card reader. 

1.  Install the HID Reader Manager app on a device that has Bluetooth. 
2.  Open the app and tap 

Scan For Readers

3.  Tap the reader that you want to configure. 
4.  Tap 

Software

 and tap 

Configure

5.  Tap 

Inspect

. Follow the instructions on the screen. 

6.  Tap 

Detailed

 

Configuration

 and tap 

Communication

 

Protocol

7.  Tap 

Host

 

Protocol

 and enable 

OSDP

8.  In the 

ADDRESS

 field, enter an address. Addresses start at 0 in EntraPass. Refer to 

your EntraPass system for the next available address. 

9.  Tap 

ADD TO TEMPLATE

10. In the 

OSDP BAUD RATE

 field, enter the baud rate that you configured in 

EntraPass. 