Installation
2–18
iSTAR Ultra Installation and Configuration Guide
IP-ACM Installation
The IP-ACM is mounted separately from the Ultra GCM in a plastic or metal enclosure. The
following sections describe the enclosures and their installation with the IP-ACM board.
Plastic Enclosure
Figure 2-2:
Plastic Enclosure for the IP-ACM
Requirements
The anchoring system must be capable of sustaining 25lb (11.4kg). This weight does not
include the cables.
The cables are protected by use of conduit, which is metal, plastic, or flexible cable grip
strain relief.
12VDC or 24VDC local power or Power over Ethernet (PoE or PoE+)
.
NOTE
See the
IP-ACM Ethernet Door Module Quick Start Guide
for power and
cabling
requirements.
Table 2-12:
IP-ACM and Reader Plastic Enclosure Dimensions
Item
Dimension
Weight
2.2lb (1kg)
Height
12.1in (307mm)
Width
7.2in (183mm)
Depth
2.46in (62.4mm)