Model CWS Specific Application 

Concealed Pendent Vertical Sidewall  

Window Sprinkler 5.6 K-factor

Page 1 of 8 

DECEMBER 2019 

TFP621

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Model CWS Specific Appli-

cation Concealed Pendent Vertical 

Sidewall Window Sprinkler is a fast 

response, solder-link type sprinkler 

which delivers water to window glazing 

in a horizontal pattern.
This sprinkler is the first concealed 

window sprinkler to be specifically 

Listed to provide complete wetting and 

coverage for heat strengthened, tem-

pered, or ceramic glass windows using 

closed sprinklers. As part of the testing, 

the gas flow required to achieve the 

time/temperature relationship speci-

fied in ASTM E119 was established in 

a test furnace without sprinkler pro-

tection. A window assembly protected 

with the Model CWS Window Sprinkler 

was then installed in the test furnace, 

and the same gas flow conditions were 

maintained for a two-hour test period. 

No cracking or visible damage to the 

window was permitted during the test 

period.
The success of the Model CWS Window 

Sprinkler is based on its fast response 

thermal sensitivity and on its specially 

designed deflector which ensures the 

spray pattern wets the entire surface 

of the window.
Based on successful testing, the Model 

CWS Window Sprinkler can be used 

as interior protection for windows or 

glazing in a sprinklered building or 

non-sprinklered building in accordance 

with Section 104 of the IBC (“Alternate 

Materials, Design and Methods of Con-

struction and Equipment”).
As with any specific application sprin-

kler, the installation instructions 

included in this data sheet must be pre-

cisely followed. If there are additional 

local or jurisdictional installation stan-

dards/codes for window sprinklers on 

glazed window systems, this document 

does not relieve the designer/installer 

from these requirements. Consult your 

local jurisdiction to verify if or when 

these additional guidelines must be 

followed.

NOTICE

TYCO Model CWS Specific Applica-

tion Window Sprinkler described herein 

must be installed and maintained in 

compliance with this document, as 

well as with the applicable standards 

recognized by the approval agency, in 

addition to the standards of any author-

ities having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number (SIN)

TY3498

Technical 

Data

Approvals

UL and C-UL Listed

Additional Recognition

ICC Evaluation Service (ESR-2397)

Pipe Thread Connection

1/2 in. NPT

Discharge Coefficient

K=5.6 GPM/psi

½

 (80,6 LPM/bar

½

)

Temperature Ratings

160°F (71°C) Sprinkler with 

139

°

F (59

°

C) Cover Plate

212°F (100°C) Sprinkler with 

165°F (74°C) Cover Plate

Finish

See Ordering Procedure section

Physical Characteristics

Body  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Saddle . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Soldered Link Halves . . . . . . . . . . . . . . . .  Nickel

Lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . Brass/Bronze

Guide Pin Housing  . . . . . . . . . . . . . . . . . .Bronze

Guide Pins  . . . . . . . . . . . . . . . . .  Stainless Steel

Support Cup   . . . . . . . . . . . . . . . . . . . . . . .  Steel

Cover Plate  . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Retainer  . . . . . . . . . . . . . . . . . . . . . . . . .  Copper

Cover Plate Ejection Spring  . . . . Stainless Steel

Summary of Contents for tyco CWS

Page 1: ...Model CWS Window Sprinkler can be used as interior protection for windows or glazing in a sprinklered building or non sprinklered building in accordance with Section 104 of the IBC Alternate Material...

Page 2: ...ORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING LEVER SADDLE CAP DEFLECTOR 3 3 16 DIA 81 0 mm 2 1 2 DIA 63 5 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING DEFLECTOR IN OPERATED POSITION DISPOSABL...

Page 3: ...stem Protection Type Interior Wet Systems Glass Type The following types and thicknesses of glass are recognized for use with the Model CWS Window Sprinkler Non operable heat strengthened tempered sin...

Page 4: ...ilized the linear length of the calculated window sprinklers may be reduced but in no case shall be less than 36 linear feet 1 2 x 900 If a single fire can be expected to operate Model CWS Window Spri...

Page 5: ...listed to protect windows when intermediate horizontal mullions are present 4 0 1 22 m MAXIMUM 0 4 101 6 mm MINIMUM 8 0 2 44 m MAXIMUM MODEL CWS CONCEALED SPRINKLER 6 0 1 83 m MINIMUM MULLION Minimum...

Page 6: ...E THROUGH USE OF 3 0 0 9 m MINIMUM PONY WALL INSTALLATION NOTE MODEL CWS SPRINKLER SHOWN ON ONE SIDE OF GLAZING FOR CLARITY FOR GLASS TYPES OTHER THAN FIRELITE PLUS CWS CERAMIC GLASS BY TGP ALL COMBUS...

Page 7: ...nnot be engaged sufficiently to contact the ceiling the Sprinkler Fitting must be repositioned Care and Maintenance The TYCO Model CWS Specific Appli cation Window Sprinkler must be main tained and se...

Page 8: ...temperature rating and P N specify 160 F 71 C 50 630 0 160 212 F 100 C 50 630 0 212 Note Sprinkler and Cover Plates are sepa rately sold See Cover Plate Assemblies subsection for ordering information...