background image

Ultra Low Flow AQUAMIST Nozzles 

Type ULF AM29 

Automatic (Closed)

Page 1 of 4 

AUGUST 2018 

TFP2229

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

Physical Characteristics

Frame  � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Brass 

Strainer � � � � � � � � � � � � � � � � � � � � � � � � � �  Copper 

Orifice Insert � � � � � � � � � � � � � � � � � � � � � � �Bronze 

Button � � � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze 

Sealing Assembly  � �Beryllium Nickel w/TEFLON 

Ejection Spring � � � � � � � � � � � � � �  Stainless Steel 

Bulb � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � Glass 

Diffuser � � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze 

Loading Screw  � � � � � � � � � � � � � � � � � � � � �Bronze

The smallest waterway (orifice) diam-

eter of the Orifice Insert is nominally 

4,4 mm (0�172 inches)� The diameter of 

the Inlet Strainer perforations is nomi-

nally 3,2 mm (0�125 inches)�

The design of individual water mist 

systems can vary considerably, 

depending on the characteristics and 

nature of the hazard and the basic 

purpose of the water mist system. 

Because of these variations, the design 

of water mist systems for fire protec-

tion must only be performed by expe-

rienced designers who thoroughly 

understand the limitations as well as 

capabilities of such systems.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Approvals

The TYCO Type ULF AM29 AQUA-

MIST Nozzle in a 57°C (135°F) 

temperature rating and in a Natural 

Brass finish is FM Approved when 

used as part of a wet pipe system in 

HC-1 applications� The TYCO Type 

ULF AM29 AQUAMIST Nozzle in 57°C 

(135°F) and 68°C (155°C) temperature 

ratings and in a Natural Brass finish 

is FM Approved when used as part of 

a wet pipe or single-interlock pre-

action system in protection of data 

processing equipment rooms/halls� 

In particular, the FM Approval testing 

was performed in accordance with 

FM Class 5560, “Approval Standard 

for Water Mist Systems�”

Technical 

Data

Discharge Coefficient

K=8,5 lpm/bar

1/2

 (K=0�59 gpm/psi

1/2

)

Thread Connection

1/2 Inch NPT

Finishes

Natural Brass 

Pure White 

Signal White 

Chrome Plated

Temperature Ratings

Refer to Table A

General 

Description

TYCO Ultra Low Flow AQUAMIST 

Nozzles Type ULF AM29 are closed 

(automatic) nozzles intended for use 

with engineered, water mist systems� 

They are low-pressure nozzles that 

utilize a single fluid jet impinging on a 

diffuser to produce a spray having a 

range of water droplet sizes suitable 

for the control of Class A fires and the 

protection of data centers�
It is recommended that the end user be 

consulted with respect to the suitabil-

ity of the materials of construction and 

finish for any given corrosive environ-

ment� The effects of ambient tempera-

ture, concentration of chemicals, and 

gas/chemical velocity should be con-

sidered, at a minimum, along with the 

corrosive nature to which the nozzles 

may be exposed�

NOTICE

The Type ULF AM29 AQUAMIST 

Nozzles de scribed herein must be 

installed and maintained in compliance 

with this document and with the appli-

cable standards of the NATIONAL FIRE 

PROTECTION ASSOCIATION (NFPA), 

in addition to the standards of any 

authorities having jurisdiction. Failure 

to do so may impair the performance 

of these devices.

Temperature 

Rating

Bulb 

Fluid Color

57

°

C (135

°

F)

Orange

68

°

C (155

°

F)

Red

79

°

C (175

°

F)

Yellow

93

°

C (200

°

F)

Green

141

°

C (286

°

F)

Blue

182

°

C (360

°

F)

Mauve

TABLE A 

TEMPERATURE RATING 

SELECTION

Reviews: