Ultra Low Flow AQUAMIST Nozzles
Type ULF AM29
Automatic (Closed)
Page 1 of 4
AUGUST 2018
TFP2229
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
Physical Characteristics
Frame � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Brass
Strainer � � � � � � � � � � � � � � � � � � � � � � � � � � Copper
Orifice Insert � � � � � � � � � � � � � � � � � � � � � � �Bronze
Button � � � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze
Sealing Assembly � �Beryllium Nickel w/TEFLON
Ejection Spring � � � � � � � � � � � � � � Stainless Steel
Bulb � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � Glass
Diffuser � � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze
Loading Screw � � � � � � � � � � � � � � � � � � � � �Bronze
The smallest waterway (orifice) diam-
eter of the Orifice Insert is nominally
4,4 mm (0�172 inches)� The diameter of
the Inlet Strainer perforations is nomi-
nally 3,2 mm (0�125 inches)�
The design of individual water mist
systems can vary considerably,
depending on the characteristics and
nature of the hazard and the basic
purpose of the water mist system.
Because of these variations, the design
of water mist systems for fire protec-
tion must only be performed by expe-
rienced designers who thoroughly
understand the limitations as well as
capabilities of such systems.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Approvals
The TYCO Type ULF AM29 AQUA-
MIST Nozzle in a 57°C (135°F)
temperature rating and in a Natural
Brass finish is FM Approved when
used as part of a wet pipe system in
HC-1 applications� The TYCO Type
ULF AM29 AQUAMIST Nozzle in 57°C
(135°F) and 68°C (155°C) temperature
ratings and in a Natural Brass finish
is FM Approved when used as part of
a wet pipe or single-interlock pre-
action system in protection of data
processing equipment rooms/halls�
In particular, the FM Approval testing
was performed in accordance with
FM Class 5560, “Approval Standard
for Water Mist Systems�”
Technical
Data
Discharge Coefficient
K=8,5 lpm/bar
1/2
(K=0�59 gpm/psi
1/2
)
Thread Connection
1/2 Inch NPT
Finishes
Natural Brass
Pure White
Signal White
Chrome Plated
Temperature Ratings
Refer to Table A
General
Description
TYCO Ultra Low Flow AQUAMIST
Nozzles Type ULF AM29 are closed
(automatic) nozzles intended for use
with engineered, water mist systems�
They are low-pressure nozzles that
utilize a single fluid jet impinging on a
diffuser to produce a spray having a
range of water droplet sizes suitable
for the control of Class A fires and the
protection of data centers�
It is recommended that the end user be
consulted with respect to the suitabil-
ity of the materials of construction and
finish for any given corrosive environ-
ment� The effects of ambient tempera-
ture, concentration of chemicals, and
gas/chemical velocity should be con-
sidered, at a minimum, along with the
corrosive nature to which the nozzles
may be exposed�
NOTICE
The Type ULF AM29 AQUAMIST
Nozzles de scribed herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
Temperature
Rating
Bulb
Fluid Color
57
°
C (135
°
F)
Orange
68
°
C (155
°
F)
Red
79
°
C (175
°
F)
Yellow
93
°
C (200
°
F)
Green
141
°
C (286
°
F)
Blue
182
°
C (360
°
F)
Mauve
TABLE A
TEMPERATURE RATING