background image

TEC22x2-3 L

ON

W

ORKS

® Networked Heat Pump Thermostat Installation Instructions

10

Comf/eco

Selects how the auxiliary heat is 
used.
Default: 

comfort

(economy) – 

in the heating mode: If the heat pump is not able to 

satisfy the heating setpoint, the auxiliary heat is energized to satisfy 
the setpoint only when the temperature has dropped 2F°/1C° below 
the heating setpoint.

Note:

Selecting economy in the heating mode adds a deadband 
between the heat pump and auxiliary heat. The actual 
temperature maintained is lower than the true heating 
setpoint to maximize the heat pump operation. When the 
outdoor air temperature drops below the low balance point, 
the deadband is eliminated.

(economy) –

 in the emergency heat mode: The setpoint that is 

maintained is the heating setpoint.

(comfort) –

 in the heating mode: If the heat pump is not able to 

satisfy the heating setpoint, the auxiliary heat is energized to satisfy 
the setpoint.

Re valve

Governs the reversing valve 
operation.
Default: 

O

(B):

 Energizes the valve in heating operation (valve is normally cool)

(O):

 Energizes the valve in cooling operation (valve is normally heat)

Comp/aux

Sets the mode of interaction 
between the heat pump and the 
auxiliary heat.
Default:

 off

(on) –

 in the heating mode only: If the heat pump is not able to 

satisfy the heating setpoint, the auxiliary heat is energized and the 
heat pump is shut off. This typically applies when the air handler 
heat pump coil is installed after the auxiliary heat. There is a 
2-minute delay to restart the heat pump after the auxiliary heat is 
shut down.

(off) –

 in the heating mode only: If the heat pump is not able to 

satisfy the heating setpoint, the auxiliary heat is energized at the 
same time as the heat pump stage. This typically applies when the 
air handler heat pump coil is installed before the auxiliary heat (all 
electric systems).

1.

Setting DI1 or DI2 to RemNSB disables schedules and stops the Schedule menu display. Any other setting enables 
schedules and the Schedule menu. (TEC2262-3 only)

2.

When adjusting the numeric value, press the 

UP

 or 

DOWN

 arrow key to change the value by single increments; press and 

hold the 

UP

 or 

DOWN

 arrow key to change the numeric value in increments of ten.

3.

When adjusting the temperature, press the 

UP

 or 

DOWN

 arrow key to change the value in 0.5F°/0.5C° increments; press 

and hold the 

UP

 or 

DOWN

 arrow key to change the value in 5.0F°/5.0C° increments.

4.

When the outdoor air sensor is not connected or it has a short, the thermostat bypasses heating lockout, cooling lockout, 
high balance point, and low balance point. Emergency mode bypasses heating lockout and permits auxiliary heating 
whenever a heating demand occurs.

5.

TEC2262-3 only

Table 2:  Installer Configuration Menu  (Part 5 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Summary of Contents for TEC22 2-3 LonWorks Series

Page 1: ...appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x2 3 thermostat on a partitioning...

Page 2: ...into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing thermostat...

Page 3: ...Table 1 Terminal Identification See Figure 5 Number Label Function 1 Y2 Energizes second stage compressor on a call for heating or cooling 2 Y1 Energizes first stage compressor on a call for heating o...

Page 4: ...k wiring in the same conduit as line voltage wiring 30 VAC or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators The LONWORKS network req...

Page 5: ...el when the thermostat is left unattended for 45 seconds Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The FAN LED is on when the fan...

Page 6: ...the UP DOWN arrow keys simultaneously for 5 seconds to broadcast the thermostat s Neuron Identification on the LONWORKS network If the cover is removed you can see a green LED under the LON board fla...

Page 7: ...ccess No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Schedules Setting5 Access No Access No Access Clock Setting5 Access Access Access Pwr del2 Se...

Page 8: ...ycle has ended The fan delay is only active when the fan is in the Auto mode TOccTime Sets the duration of the Temporary Occupancy Time when the thermostat is in the Unoccupied mode when a Schedule Ov...

Page 9: ...desired occupied temperature either at the start of the occupied schedule or after the occupied schedule begins Note Progressive recovery is disabled if either DI1 or DI2 is configured as remote NSB D...

Page 10: ...auxiliary heat is energized and the heat pump is shut off This typically applies when the air handler heat pump coil is installed after the auxiliary heat There is a 2 minute delay to restart the heat...

Page 11: ...at is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupi...

Page 12: ...ess the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return...

Page 13: ...e to change the time in 1 minute increments press and hold down the keys to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB disables the menu Table 4 P...

Page 14: ...ess the UP DOWN arrow keys to set the first unoccupied start time Press the YES key to enter the time RoomTemp 75 0 F Schedule set Y N Monday set Y N Occupied day Y N Occupied 12 00 AM Unoccup 12 00 A...

Page 15: ...ess the YES key to store the day 6 Press the YES key to choose the time format or press the NO key to access the Main User Menu exit prompt 7 Press the UP DOWN arrow keys to select the desired time fo...

Page 16: ...voltage between RC and C to be from 19 30 VAC 2 Check for tripped fuse or circuit breaker Overloaded power transformer Verify that the transformer used is powerful enough enough VAs to supply all con...

Page 17: ...splay Replace the thermostat Auxiliary heat does not operate Wrong mode selected Select Emergency Heat mode Thermostat in Unoccupied mode Select Override to force the thermostat Occupied heating setpo...

Page 18: ...essages Display Function Service Indicates that there is a service alarm in accordance with the programmable Digital Inputs DI1 or DI2 Filter Indicates that the filter s is dirty in accordance with th...

Page 19: ...pliant to CFR 47 Part 15 Subpart B Class A LONMARK Certification 3 4 pending Canada UL Listed File E27734 CCN XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Industry C...

Reviews: