® Networked Heat Pump Thermostat Installation

Instructions

1

Applications

The TEC2202-3 non-programmable and 
TEC2262-3 programmable thermostats are 
L

ON

W

ORKS

® networked devices that provide control of 

heat pump equipment. The technologically advanced 
TEC22x2-3 thermostats feature a Building Automation 
System (BAS) L

ON

W

ORKS

 network communication 

capability that enables remote monitoring and 
programmability for efficient space temperature control.  

North American Emissions Compliance

United States

This equipment has been tested and found to comply 
with the limits for a Class A digital device pursuant to 
Part 15 of the FCC Rules. These limits are designed to 
provide reasonable protection against harmful 
interference when this equipment is operated in a 
commercial environment. This equipment generates, 
uses, and can radiate radio frequency energy and, if 
not installed and used in accordance with the 
instruction manual, may cause harmful interference to 
radio communications. Operation of this equipment in a 
residential area is likely to cause harmful interference, 
in which case the user will be required to correct the 
interference at his/her own expense.

Canada

This Class (A) digital apparatus meets all the 
requirements of the Canadian Interference-Causing 
Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte 
toutes les exigences du Règlement sur le matériel 
brouilleur du Canada.

Installation

Location Considerations

Locate the TEC22x2-3 thermostat:

on a partitioning wall, approximately 5 ft (1.5 m) 
above the floor in a location of average 
temperature

away from direct sunlight, radiant heat, outside 
walls, behind doors, air discharge grills, stairwells, 
or outside doors

away from steam or water pipes, warm air stacks, 
unconditioned areas (not heated or cooled), or 
sources of electrical interference

Note:

Allow for vertical air circulation to the 

TEC22x2-3 thermostat.

To install the thermostat:

1.

Use a Phillips-head screwdriver to remove the 
security screw on the bottom of the thermostat 
cover.

2.

Pull the bottom edge of the thermostat cover and 
open the thermostat as illustrated in Figure 1. 

IMPORTANT:

The TEC22x2-3 thermostat is 

intended to provide an input to equipment under 
normal operating conditions. Where failure or 
malfunction of the thermostat could lead to personal 
injury or property damage to the controlled 
equipment or other property, additional precautions 
must be designed into the control system. 
Incorporate and maintain other devices such as 
supervisory or alarm systems or safety or limit 
controls intended to warn of, or protect against, 
failure or malfunction of the thermostat. 

Figure 1: Removing the Thermostat Cover

F

IG

:c

v

r_

rm

v

l

TEC22x2-3 L

ON

W

ORKS

® Networked Heat Pump Thermostat

Installation Instructions

Part No. 24-9890-471, Rev. —

Issued September 8, 2006

Summary of Contents for TEC22 2-3 LonWorks Series

Page 1: ...appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x2 3 thermostat on a partitioning...

Page 2: ...into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing thermostat...

Page 3: ...Table 1 Terminal Identification See Figure 5 Number Label Function 1 Y2 Energizes second stage compressor on a call for heating or cooling 2 Y1 Energizes first stage compressor on a call for heating o...

Page 4: ...k wiring in the same conduit as line voltage wiring 30 VAC or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators The LONWORKS network req...

Page 5: ...el when the thermostat is left unattended for 45 seconds Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The FAN LED is on when the fan...

Page 6: ...the UP DOWN arrow keys simultaneously for 5 seconds to broadcast the thermostat s Neuron Identification on the LONWORKS network If the cover is removed you can see a green LED under the LON board fla...

Page 7: ...ccess No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Schedules Setting5 Access No Access No Access Clock Setting5 Access Access Access Pwr del2 Se...

Page 8: ...ycle has ended The fan delay is only active when the fan is in the Auto mode TOccTime Sets the duration of the Temporary Occupancy Time when the thermostat is in the Unoccupied mode when a Schedule Ov...

Page 9: ...desired occupied temperature either at the start of the occupied schedule or after the occupied schedule begins Note Progressive recovery is disabled if either DI1 or DI2 is configured as remote NSB D...

Page 10: ...auxiliary heat is energized and the heat pump is shut off This typically applies when the air handler heat pump coil is installed after the auxiliary heat There is a 2 minute delay to restart the heat...

Page 11: ...at is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupi...

Page 12: ...ess the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return...

Page 13: ...e to change the time in 1 minute increments press and hold down the keys to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB disables the menu Table 4 P...

Page 14: ...ess the UP DOWN arrow keys to set the first unoccupied start time Press the YES key to enter the time RoomTemp 75 0 F Schedule set Y N Monday set Y N Occupied day Y N Occupied 12 00 AM Unoccup 12 00 A...

Page 15: ...ess the YES key to store the day 6 Press the YES key to choose the time format or press the NO key to access the Main User Menu exit prompt 7 Press the UP DOWN arrow keys to select the desired time fo...

Page 16: ...voltage between RC and C to be from 19 30 VAC 2 Check for tripped fuse or circuit breaker Overloaded power transformer Verify that the transformer used is powerful enough enough VAs to supply all con...

Page 17: ...splay Replace the thermostat Auxiliary heat does not operate Wrong mode selected Select Emergency Heat mode Thermostat in Unoccupied mode Select Override to force the thermostat Occupied heating setpo...

Page 18: ...essages Display Function Service Indicates that there is a service alarm in accordance with the programmable Digital Inputs DI1 or DI2 Filter Indicates that the filter s is dirty in accordance with th...

Page 19: ...pliant to CFR 47 Part 15 Subpart B Class A LONMARK Certification 3 4 pending Canada UL Listed File E27734 CCN XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Industry C...