TEC22x2-3 L
ON
W
ORKS
® Networked Heat Pump Thermostat Installation
Instructions
1
Applications
The TEC2202-3 non-programmable and
TEC2262-3 programmable thermostats are
L
ON
W
ORKS
® networked devices that provide control of
heat pump equipment. The technologically advanced
TEC22x2-3 thermostats feature a Building Automation
System (BAS) L
ON
W
ORKS
network communication
capability that enables remote monitoring and
programmability for efficient space temperature control.
North American Emissions Compliance
United States
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when this equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the
instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference,
in which case the user will be required to correct the
interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Location Considerations
Locate the TEC22x2-3 thermostat:
•
on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature
•
away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
•
away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
Note:
Allow for vertical air circulation to the
TEC22x2-3 thermostat.
To install the thermostat:
1.
Use a Phillips-head screwdriver to remove the
security screw on the bottom of the thermostat
cover.
2.
Pull the bottom edge of the thermostat cover and
open the thermostat as illustrated in Figure 1.
IMPORTANT:
The TEC22x2-3 thermostat is
intended to provide an input to equipment under
normal operating conditions. Where failure or
malfunction of the thermostat could lead to personal
injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices such as
supervisory or alarm systems or safety or limit
controls intended to warn of, or protect against,
failure or malfunction of the thermostat.
Figure 1: Removing the Thermostat Cover
F
IG
:c
v
r_
rm
v
l
TEC22x2-3 L
ON
W
ORKS
® Networked Heat Pump Thermostat
Installation Instructions
Part No. 24-9890-471, Rev. —
Issued September 8, 2006