® Networked Heat Pump Thermostat Installation Instructions

2

3.

Carefully pull the locking tabs on the right side of 
the thermostat mounting base and unlock the 
Printed Circuit Board (PCB). Open the PCB to the 
left as illustrated in Figure 2. 

4.

Pull approximately 6 in. (152 mm) of wire from the 
wall and insert the wire through the hole in the 
thermostat mounting base.

5.

Align the thermostat mounting base on the wall and 
use the base as a template to mark the two 
mounting hole locations.

Note:

Be sure to position the thermostat mounting 

base so that the arrow on the base points upward 
to indicate the top of the thermostat.

6.

Drill a 3/16 in. (5 mm) hole at each of the two 
marked locations and tap nylon anchors (included 
with the thermostat) flush to the wall surface.

7.

Position the thermostat mounting base on the wall 
and use the two mounting screws (included with 
the thermostat) to secure the base to the surface 
as illustrated in Figure 3.

Note:

Be careful not to overtighten the mounting 

screws. 

8.

Swing the PCB back to the right and carefully snap 
it into the locking tabs on the thermostat mounting 
base.

9.

Pull the pull tabs on each of the connectors and 
remove the screw terminal blocks as illustrated in 
Figure 4. 

Wiring

When an existing thermostat is replaced, remove and 
label the wires to identify the terminal functions. When 
a TEC22x2-3 thermostat is replaced, simply remove 
the old screw terminal blocks and reinsert them onto 
the PCB of the replacement thermostat.        

To wire the thermostat:

1.

Strip the ends of each wire 1/4 in. (6 mm) and 
connect them to the appropriate screw terminals as 
indicated in Figure 5 and Figure 7.

Figure 2: Opening the Thermostat PCB

PCB
Locking
Tabs

F

IG

:p

rn

td

_

c

rc

t_

b

rd

Figure 3: Securing the Thermostat 

Mounting Base to the Wall

F

IG

:m

n

tn

g

_

b

s

!

CAUTION: Risk of Electric Shock.

Disconnect the power supply before 
making electrical connections to avoid 
electric shock. 

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment. 

IMPORTANT:

Make all wiring connections in 

accordance with local, national, and regional 
regulations. Do not exceed the electrical ratings of 
the TEC22x2-3 thermostat.

Figure 4: Removing the Screw Terminal Blocks

F

IG

:t

rm

n

l_

b

lc

k

s

Summary of Contents for TEC22 2-3 LonWorks Series

Page 1: ...appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x2 3 thermostat on a partitioning...

Page 2: ...into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing thermostat...

Page 3: ...Table 1 Terminal Identification See Figure 5 Number Label Function 1 Y2 Energizes second stage compressor on a call for heating or cooling 2 Y1 Energizes first stage compressor on a call for heating o...

Page 4: ...k wiring in the same conduit as line voltage wiring 30 VAC or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators The LONWORKS network req...

Page 5: ...el when the thermostat is left unattended for 45 seconds Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The FAN LED is on when the fan...

Page 6: ...the UP DOWN arrow keys simultaneously for 5 seconds to broadcast the thermostat s Neuron Identification on the LONWORKS network If the cover is removed you can see a green LED under the LON board fla...

Page 7: ...ccess No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Schedules Setting5 Access No Access No Access Clock Setting5 Access Access Access Pwr del2 Se...

Page 8: ...ycle has ended The fan delay is only active when the fan is in the Auto mode TOccTime Sets the duration of the Temporary Occupancy Time when the thermostat is in the Unoccupied mode when a Schedule Ov...

Page 9: ...desired occupied temperature either at the start of the occupied schedule or after the occupied schedule begins Note Progressive recovery is disabled if either DI1 or DI2 is configured as remote NSB D...

Page 10: ...auxiliary heat is energized and the heat pump is shut off This typically applies when the air handler heat pump coil is installed after the auxiliary heat There is a 2 minute delay to restart the heat...

Page 11: ...at is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupi...

Page 12: ...ess the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return...

Page 13: ...e to change the time in 1 minute increments press and hold down the keys to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB disables the menu Table 4 P...

Page 14: ...ess the UP DOWN arrow keys to set the first unoccupied start time Press the YES key to enter the time RoomTemp 75 0 F Schedule set Y N Monday set Y N Occupied day Y N Occupied 12 00 AM Unoccup 12 00 A...

Page 15: ...ess the YES key to store the day 6 Press the YES key to choose the time format or press the NO key to access the Main User Menu exit prompt 7 Press the UP DOWN arrow keys to select the desired time fo...

Page 16: ...voltage between RC and C to be from 19 30 VAC 2 Check for tripped fuse or circuit breaker Overloaded power transformer Verify that the transformer used is powerful enough enough VAs to supply all con...

Page 17: ...splay Replace the thermostat Auxiliary heat does not operate Wrong mode selected Select Emergency Heat mode Thermostat in Unoccupied mode Select Override to force the thermostat Occupied heating setpo...

Page 18: ...essages Display Function Service Indicates that there is a service alarm in accordance with the programmable Digital Inputs DI1 or DI2 Filter Indicates that the filter s is dirty in accordance with th...

Page 19: ...pliant to CFR 47 Part 15 Subpart B Class A LONMARK Certification 3 4 pending Canada UL Listed File E27734 CCN XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Industry C...