background image

TEC22x2-3 L

ON

W

ORKS

® Networked Heat Pump Thermostat Installation Instructions

16

Accessories

All the accessories in Table 7 include mounting 
hardware; contact the nearest Johnson Controls® 
representative to order any of these parts.

Note:

Review the technical specifications of the 

optional accessories prior to their use in an application.

Repair Information

If the TEC22x2-3 thermostat fails to operate within its 
specifications, see Table 8 for troubleshooting details 
and Table 9 for display messaging. For a replacement 
thermostat, contact the nearest Johnson Controls 
representative.

    

 

 

   

Table 7:  Accessories (Order Separately)

Code Number

Description

SEN-600-1

Remote Indoor Air Temperature Sensor

SEN-600-4

Remote Indoor Air Temperature Sensor with Occupancy Override and LED

TE-6361M-1

1

Duct Mount Air Temperature Sensor

TE-636S-1

1

Strap-on Temperature Sensor

1.

Additional TE-636xx-x Series 10k Type II Thermistor Sensors are available; refer to the 

TE-6300 Series Temperature 

Sensors Product Bulletin (LIT-216320)

 for more details.

Table 8:  Troubleshooting Details (Part 1 of 3)

Symptom

Cause

Solution(s)

No display on the 
thermostat

Absent or incorrect 
supply voltage

1. Check power supply voltage between RC and C to be from 19-30 VAC.
2. Check for tripped fuse or circuit breaker.

Overloaded power 
transformer

Verify that the transformer used is powerful enough (enough VAs) to supply all 
controlled devices including the thermostat.

Keyboard menu 
does not access all 
functions

Keyboard locked

1. Use the Installer Configuration menu to change the Lockout level to 0 or 1. 
2. Change the nciGenOpts Byte 27(28) lockout value to 0 or 1.

Temperature 
setpoints revert to 
original value after 
a certain time

Temporary setpoint 
active for a period of 
time set by 
parameter 
TOccTime

To do a permanent change to the setpoints you must enter the menu 

RoomTemp Set

 and modify the setpoints at desired temperature.

Thermostat does 
not call for heating

Wrong mode 
selected

Select heating mode.

Thermostat in 
Unoccupied mode

Select Override to force the thermostat Occupied heating setpoint.

Anticycle delay 
active

Wait, the anticycling period must end before the equipment can start.

Heating setpoint is 
satisfied

Raise the Heating setpoint.

Heating lockout 
attained 

Mode is locked out based on outside air temperature.
Change configuration parameter H Lock to value 120°F (49°C) to by-pass 
lockout.

Wiring error 

Start the fan by forcing the Fan ON mode.
Put a jumper across terminals RH & W1. The heating should come ON. If it 
does not, verify wiring and check if a jumper is required between RC & RH.

Summary of Contents for TEC22 2-3 LonWorks Series

Page 1: ...appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x2 3 thermostat on a partitioning...

Page 2: ...into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing thermostat...

Page 3: ...Table 1 Terminal Identification See Figure 5 Number Label Function 1 Y2 Energizes second stage compressor on a call for heating or cooling 2 Y1 Energizes first stage compressor on a call for heating o...

Page 4: ...k wiring in the same conduit as line voltage wiring 30 VAC or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators The LONWORKS network req...

Page 5: ...el when the thermostat is left unattended for 45 seconds Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The FAN LED is on when the fan...

Page 6: ...the UP DOWN arrow keys simultaneously for 5 seconds to broadcast the thermostat s Neuron Identification on the LONWORKS network If the cover is removed you can see a green LED under the LON board fla...

Page 7: ...ccess No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Schedules Setting5 Access No Access No Access Clock Setting5 Access Access Access Pwr del2 Se...

Page 8: ...ycle has ended The fan delay is only active when the fan is in the Auto mode TOccTime Sets the duration of the Temporary Occupancy Time when the thermostat is in the Unoccupied mode when a Schedule Ov...

Page 9: ...desired occupied temperature either at the start of the occupied schedule or after the occupied schedule begins Note Progressive recovery is disabled if either DI1 or DI2 is configured as remote NSB D...

Page 10: ...auxiliary heat is energized and the heat pump is shut off This typically applies when the air handler heat pump coil is installed after the auxiliary heat There is a 2 minute delay to restart the heat...

Page 11: ...at is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupi...

Page 12: ...ess the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return...

Page 13: ...e to change the time in 1 minute increments press and hold down the keys to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB disables the menu Table 4 P...

Page 14: ...ess the UP DOWN arrow keys to set the first unoccupied start time Press the YES key to enter the time RoomTemp 75 0 F Schedule set Y N Monday set Y N Occupied day Y N Occupied 12 00 AM Unoccup 12 00 A...

Page 15: ...ess the YES key to store the day 6 Press the YES key to choose the time format or press the NO key to access the Main User Menu exit prompt 7 Press the UP DOWN arrow keys to select the desired time fo...

Page 16: ...voltage between RC and C to be from 19 30 VAC 2 Check for tripped fuse or circuit breaker Overloaded power transformer Verify that the transformer used is powerful enough enough VAs to supply all con...

Page 17: ...splay Replace the thermostat Auxiliary heat does not operate Wrong mode selected Select Emergency Heat mode Thermostat in Unoccupied mode Select Override to force the thermostat Occupied heating setpo...

Page 18: ...essages Display Function Service Indicates that there is a service alarm in accordance with the programmable Digital Inputs DI1 or DI2 Filter Indicates that the filter s is dirty in accordance with th...

Page 19: ...pliant to CFR 47 Part 15 Subpart B Class A LONMARK Certification 3 4 pending Canada UL Listed File E27734 CCN XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Industry C...

Reviews: