Figure 1: Removing the Thermostat Cover 

PCB

Locking Tabs

fi

g

2

-b

 

Figure 2: Opening the Thermostat PCB 

fi

g3-

b

 

Figure 3: Mounting the Thermostat Base 

fi

g4-

a

 

Figure 4: Removing the Terminal Blocks 

Wiring 

!

  CAUTION:  Risk of Electric Shock.

 

Disconnect power supply before making electrical 
connections to avoid electric shock.

 

 

Note: 

When replacing an existing thermostat, 

remove and label wires to identify terminal 
designations. When replacing a TEC2104-1 
thermostat, simply remove the terminal blocks and 
reinsert onto the new thermostat. 

To wire the thermostat: 

1.  Strip each wire 1/4 in. (6.35 mm) and connect to 

the appropriate terminal according to the 
TEC2104-1 wiring diagram (Figure 5). 

2.  Gently push excess wire back into the wall, plug 

the wall hole with fireproof material to prevent 
drafts from affecting ambient temperature 
readings, and install screw terminal blocks back 
onto the PCB. 

3.  Reattach the thermostat cover to the installed 

base (top side first) and install the security screw 
on the bottom. 

!

  CAUTION:  Risk of Property Damage. 

Do not apply power to the system before checking 
all wiring connections. Short circuited or improperly 
connected wires may result in permanent damage to 
the equipment. 

 

2

    TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions 

Summary of Contents for TEC2104-1

Page 1: ...side doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the therm...

Page 2: ...the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the TEC2104 1 wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall h...

Page 3: ...C N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM EC 0 to 10 VDC 24 VAC Common MS EC Remote Mixed Air Sensor Cool 2 fig5 b Figure...

Page 4: ...o 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP a ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP A...

Page 5: ...System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode On at the TEC keypad the TEC keeps the System Mode Off Once an over...

Page 6: ...to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note When left una...

Page 7: ...t pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Sta...

Page 8: ...tages See the Disable Enable Second Cooling Stage C Stage section Disables Heating Operation based on Auxiliary Outdoor Air Temperature Default 120 F 49 C See the Setting the Heating Lockout H lock se...

Page 9: ...the TEC2104 1 the states of DI1 and DI2 are communicated over the N2 network This enables the ability to communicate alarm conditions over the network without local annunciation on the TEC2104 1 displ...

Page 10: ...F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the minimum cooling setpoint while in the Installer Configuration Menu 1 Ans...

Page 11: ...stable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint...

Page 12: ...offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the room sensor calibration prompt appears in the display Press YES to enter the Room Sensor Calibration Menu 2 Use th...

Page 13: ...F C To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu 1 Answer NO to all prompts until the cooling lockout prompt appears in the display Press YES to ent...

Page 14: ...djust the mixed air setpoint Press YES to store the temperature The display mixed air temperature prompt is now displayed See the Displaying the Mixed Air Temperature Display section for instructions...

Page 15: ...tered It is also where any temporary setpoints are entered To enter the heating and cooling setpoints for the occupied and unoccupied modes permanent or temporary follow the steps in Table 4 When chan...

Page 16: ...set temperature Press YES to store value and advance to the next menu Press YES to change the unoccupied heating setpoint Press NO to advance to temperature display units Use the UP DOWN arrow keys t...

Page 17: ...all prompts until the system mode prompt appears in the display Press YES to set the system mode 1 Answer NO to all prompts until the fan mode prompt appears in the display Press YES to set the fan m...

Page 18: ...ine Device type is incorrect TEC2104 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Compute...

Page 19: ...ompliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide...

Reviews: