TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
21
Pband
Proportional Band used by the PI
temperature control loop of the
thermostat.
Pband is not converted with C or F
scale and is always shown with a
range of 3 to 10.
Default:
3
(
3F°/1.7C°
)
Value
F Scale Pband/C Scale Pband
3
3.0F°/1.7C°
4
4.0F°/2.2C°
5
5.0F°/2.8C°
6
6.0F°/3.3C°
7
7.0F°/3.9C°
8
8.0F°/4.4C°
9
9.0F°/5.0C°
10
10.0F°/5.6C°
Note:
The use of a larger proportional band is not to use the
thermostat as a discharge air controller device. The use of a larger
proportional band can be used to solve issues for flawed HVAC
design with basic sizing and thermostat location errors that cannot
be worked around.
Set type
Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the
UP/DOWN
arrow keys.
Default:
permnent
(temporar):
Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent):
Local changes to the heating or cooling setpoints are
permanently stored in the thermostat controller memory.
Spt Func
Determines the operation and
usage of the local setpoint interface
by the user.
Default:
Dual Stp
(Attch Stp):
Single Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. Both the heating and
cooling setpoints are changed simultaneously, while respecting the
minimum configured deadband. If one setpoint is desired over the
other, use the
MODE
key to toggle between the two setpoints.
(Dual Stp):
Dual Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. The heating and cooling
setpoints can be separated individually, allowing the minimum
configured deadband to expand. If one setpoint is desired over the
other, use the
MODE
key to toggle between the two setpoints.
TOccTime
Sets the duration of the Temporary
Occupancy Time (when the
thermostat controller is in the
Unoccupied mode) when a
Schedule Override Function is
enabled using either the Main User
Menu or BI1 or BI2 configured as a
temporary override remote contact
(RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the
UP/DOWN
arrow keys.
Default:
2.0 hrs
Range:
0.0
to
24.0 hrs
adjustable in 1-hour increments
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default:
2.0F°/1.0C°
Range:
2.0F°/1.0C°
to
5.0F°/2.5C°
(adjustable in 1.0F°/0.5C°
increments)
Table 6: Installer Configuration Menu
(Part 6 of 8)
Parameter
Appearing
on Display
Description and Default
Selection Options