background image

TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification

Capability, Fan Control, and Occupancy Sensing Capability

21

Pband

Proportional Band used by the PI 
temperature control loop of the 
thermostat.
Pband is not converted with C or F 
scale and is always shown with a 
range of 3 to 10.
Default: 

3

 (

3F°/1.7C°

)

Value

F Scale Pband/C Scale Pband

3

3.0F°/1.7C°

4

4.0F°/2.2C°

5

5.0F°/2.8C°

6

6.0F°/3.3C°

7

7.0F°/3.9C°

8

8.0F°/4.4C°

9

9.0F°/5.0C°

10

10.0F°/5.6C°

Note:

The use of a larger proportional band is not to use the 

thermostat as a discharge air controller device. The use of a larger 
proportional band can be used to solve issues for flawed HVAC 
design with basic sizing and thermostat location errors that cannot 
be worked around.

Set type

Provides the option of temporarily 
changing the heating or cooling 
setpoint by pressing the 

UP/DOWN

 

arrow keys.
Default: 

permnent

(temporar):

 Local changes to the heating or cooling setpoints are 

temporary, and remain effective for the specified TOccTime.

(permnent):

 Local changes to the heating or cooling setpoints are 

permanently stored in the thermostat controller memory.

Spt Func

Determines the operation and 
usage of the local setpoint interface 
by the user.
Default: 

Dual Stp

(Attch Stp):

 Single Occupied Setpoint Adjustment. The displayed 

setpoint is the setpoint from the last action taken by the thermostat 
controller, or the setpoint currently in use. Both the heating and 
cooling setpoints are changed simultaneously, while respecting the 
minimum configured deadband. If one setpoint is desired over the 
other, use the 

MODE

 key to toggle between the two setpoints.

(Dual Stp):

 Dual Occupied Setpoint Adjustment. The displayed 

setpoint is the setpoint from the last action taken by the thermostat 
controller, or the setpoint currently in use. The heating and cooling 
setpoints can be separated individually, allowing the minimum 
configured deadband to expand. If one setpoint is desired over the 
other, use the 

MODE

 key to toggle between the two setpoints.

TOccTime

Sets the duration of the Temporary 
Occupancy Time (when the 
thermostat controller is in the 
Unoccupied mode) when a 
Schedule Override Function is 
enabled using either the Main User 
Menu or BI1 or BI2 configured as a 
temporary override remote contact 
(RemOVR).
Sets the effective duration of the 
Temporary heating or cooling 
setpoints set using the 

UP/DOWN

arrow keys.

Default: 

2.0 hrs

Range: 

0.0

 to 

24.0 hrs

 adjustable in 1-hour increments

Deadband

Sets the minimum deadband 
between the heating and cooling 
setpoints.
Default: 

2.0F°/1.0C°

Range: 

2.0F°/1.0C°

 to 

5.0F°/2.5C°

 (adjustable in 1.0F°/0.5C° 

increments)

Table 6:  Installer Configuration Menu

 

 (Part 6 of 8)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Summary of Contents for TEC20x6-4 Series

Page 1: ...less Thermostat Controllers are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or p...

Page 2: ...Metasys System Location Guide LIT 12011294 Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Page 3: ...u have enough space for cabling and end of line devices if needed Note For surface mount applications use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the m...

Page 4: ...ire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB Note I...

Page 5: ...EC20x6H 4 PIR Series Thermostat Controller Terminals Figure 6 TEC20x6 H 4 and TEC20x6H 4 PIR Series Thermostat Controller with Separate Power Source for Auxiliary Contact FIG TEC20x6H4_SEP BI2 UI3 BI1...

Page 6: ...Aux BO5 Aux BO5 Aux Auxiliary Binary Output 8 BO3 BO3 Blank Open Heat 9 Blank BO4 AO2 Close Heat 10 Blank BO1 AO1 Open Cool 11 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 R...

Page 7: ...ting Valve 24 V Hot BO3 N C Cooling Valve FIG TEC2016H4_onoff Figure 9 Wiring TEC2026 H 4 TEC2026H 4 PIR TEC2036 H 4 and TEC2036H 4 PIR Thermostat Controllers for On Off Control Two Pipe Applications...

Page 8: ...key also allows access to the Installer Configuration Menu See the Configuring the Thermostat Controller section C F key hospitality models changes the temperature scale to either Celsius or Fahrenhe...

Page 9: ...te For models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current...

Page 10: ...tic LEDs The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup The LEDs do not light up or brighten after the initial 30 minute period Se...

Page 11: ...he UP DOWN arrow keys to choose the desired selection option 4 Press and release the center key to continue scrolling through the parameters St By Heat 69 F Occ Heat 72 F Occ Cool 75 F St By Cool 78 F...

Page 12: ...ration SeqOpera Choose the appropriate sequence of operation The modes presented are user dependent on the sequence of operation selected For two pipe applications using a changeover sensor choose the...

Page 13: ...Cooling with Reheat See Figure 18 6 and 7 Reheat 10 N O Cooling 11 N C Cooling 6 and 7 Reheat 10 Open Cooling 11 Closed Cooling 6 and 7 Reheat 10 Proportional Cooling 3 Heating with Reheat See Figure...

Page 14: ...Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling...

Page 15: ...tting Figure 22 This operation applies to the occupied mode when the fan is set to Auto Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Device Closed Device Opened Cooling Se...

Page 16: ...e fan to low speed the chilled water valve opens to the specified maximum value set by CoolMax the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint as sens...

Page 17: ...ted if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan mode A window alarm appears indicating that the window needs to be closed to resume heating or cooling These settings dis...

Page 18: ...mperature is available as a point for integration and UI3 Status is not available as a point for integration MenuScro Gives the option of having the display continuously scroll the parameters Default...

Page 19: ...Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a changeover sensor to allow changeo...

Page 20: ...from drifting from stand by mode to unoccupied mode when occupancy sensor functions are used Range 0 0 to 24 0 hours in 0 5 hour increments St By HT Sets Stand by heating setpoint when used with occu...

Page 21: ...int Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use Both the heating and cooling setpoints are changed simult...

Page 22: ...use this selection option 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxiliary functions via a separate and dedi...

Page 23: ...e acting 0 to 100 10 to 0 VDC DA Direct acting 0 to 100 0 to 10 VDC Reheat Sets the duty cycle time for reheat output if Option 2 3 or 5 is chosen in the SeqOpera parameter Default 0 1 10 seconds six...

Page 24: ...y sensing capability 5 TEC 6H PIR Accessory Cover can be used to replace the existing cover on a non PIR TEC20x6H 4 Series Thermostat Controller to provide occupancy sensing capability TEC20x6 H 4 and...

Page 25: ...le E27734 CCN XAPX Under UL 873 Temperature Indicating and Regulating Equipment FCC Compliant to Part 15 247 Regulations for Low Power Unlicensed Transmitters Transmitter FCC Identification pending Ca...

Reviews: