background image

TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification

Capability, Fan Control, and Occupancy Sensing Capability

17

Channel

Sets the mesh network channel the 
device uses for communication. 
Only devices using the same mesh 
network channel can communicate 
with each other. Default: 

10

Range: 

11

 to 

26

Note:

Setting this parameter to 10 disables the function.

GET FROM

Parameter not available at this time.

N/A

BI1

Configuration of Binary Input 1.
Default: 

None

(None):

 No function is associated with an input.

(Rem NSB):

 Remote Night Setback (NSB) via a time clock input, an 

occupancy sensor, or from a voltage-free contact. 
Contact open = Occupied; contact closed = Unoccupied.

(MotionNO*):

 Temporary occupancy request via a motion detector 

input. Contact open = Unoccupied. When the contact closes, the 
thermostat controller goes into the occupied mode for a specified 
TOccTime. Once the TOccTime begins, the thermostat controller 
remains in the occupied mode if the contact is open, until the 
TOccTime expires.

(MotionNC*):

 Temporary occupancy request via a motion detector 

input. Contact closed = Unoccupied. When the contact opens, the 
thermostat controller goes into the occupied mode for a specified 
TOccTime. Once the TOccTime begins, the thermostat controller 
remains in the occupied mode if the contact is closed, until the 
TOccTime expires.

(Window):

 Cancels the heating or cooling action when a window is 

open. The fan operation is only affected if the Fan Menu parameter 
is set to (4): On-Auto and Auto is the selected fan mode. A window 
alarm appears, indicating that the window needs to be closed to 
resume heating or cooling.
*These settings disable any local override function.

BI2

Configuration of Binary Input 2.
Default: 

None

(None):

 No function is associated with an input.

(Door Dry): 

Door contact only has an effect if BI1 is set to 

MotionNO

 or 

MotionNC.

 (See the 

BI1

 parameter earlier in this 

table.) The occupancy is now dictated via BI1 and BI2. Any motion 
detected sets the zone to Occupied status. The zone remains 
permanently in occupied mode until the door contact switch opens 
momentarily. The thermostat then enters stand-by mode. If more 
movements are detected, the occupied mode resumes. While the 
door is opened, any movements detected by the remote PIR sensor 
or the PIR accessory cover are ignored. Use a Normally Closed 
contact switching device. Contact opened = Door opened, 
Contact closed = Door closed.

(RemOVR):

 Temporary occupancy request via a remote input. This 

override function is controlled by a manual remote occupancy 
override. When enabled, this condition disables the override 
capability of the thermostat controller.

(Filter):

 A Filter alarm is displayed. This alarm can be connected to 

a differential pressure switch that monitors a filter.

(Service):

 A Service alarm is displayed on the thermostat controller 

when the input is energized. This input can be tied into the air 
conditioning unit control card, which provides an alarm should there 
be a malfunction.

Table 6:  Installer Configuration Menu

 

 (Part 2 of 8)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Summary of Contents for TEC20x6-4 Series

Page 1: ...less Thermostat Controllers are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or p...

Page 2: ...Metasys System Location Guide LIT 12011294 Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Page 3: ...u have enough space for cabling and end of line devices if needed Note For surface mount applications use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the m...

Page 4: ...ire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB Note I...

Page 5: ...EC20x6H 4 PIR Series Thermostat Controller Terminals Figure 6 TEC20x6 H 4 and TEC20x6H 4 PIR Series Thermostat Controller with Separate Power Source for Auxiliary Contact FIG TEC20x6H4_SEP BI2 UI3 BI1...

Page 6: ...Aux BO5 Aux BO5 Aux Auxiliary Binary Output 8 BO3 BO3 Blank Open Heat 9 Blank BO4 AO2 Close Heat 10 Blank BO1 AO1 Open Cool 11 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 R...

Page 7: ...ting Valve 24 V Hot BO3 N C Cooling Valve FIG TEC2016H4_onoff Figure 9 Wiring TEC2026 H 4 TEC2026H 4 PIR TEC2036 H 4 and TEC2036H 4 PIR Thermostat Controllers for On Off Control Two Pipe Applications...

Page 8: ...key also allows access to the Installer Configuration Menu See the Configuring the Thermostat Controller section C F key hospitality models changes the temperature scale to either Celsius or Fahrenhe...

Page 9: ...te For models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current...

Page 10: ...tic LEDs The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup The LEDs do not light up or brighten after the initial 30 minute period Se...

Page 11: ...he UP DOWN arrow keys to choose the desired selection option 4 Press and release the center key to continue scrolling through the parameters St By Heat 69 F Occ Heat 72 F Occ Cool 75 F St By Cool 78 F...

Page 12: ...ration SeqOpera Choose the appropriate sequence of operation The modes presented are user dependent on the sequence of operation selected For two pipe applications using a changeover sensor choose the...

Page 13: ...Cooling with Reheat See Figure 18 6 and 7 Reheat 10 N O Cooling 11 N C Cooling 6 and 7 Reheat 10 Open Cooling 11 Closed Cooling 6 and 7 Reheat 10 Proportional Cooling 3 Heating with Reheat See Figure...

Page 14: ...Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling...

Page 15: ...tting Figure 22 This operation applies to the occupied mode when the fan is set to Auto Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Device Closed Device Opened Cooling Se...

Page 16: ...e fan to low speed the chilled water valve opens to the specified maximum value set by CoolMax the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint as sens...

Page 17: ...ted if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan mode A window alarm appears indicating that the window needs to be closed to resume heating or cooling These settings dis...

Page 18: ...mperature is available as a point for integration and UI3 Status is not available as a point for integration MenuScro Gives the option of having the display continuously scroll the parameters Default...

Page 19: ...Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a changeover sensor to allow changeo...

Page 20: ...from drifting from stand by mode to unoccupied mode when occupancy sensor functions are used Range 0 0 to 24 0 hours in 0 5 hour increments St By HT Sets Stand by heating setpoint when used with occu...

Page 21: ...int Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use Both the heating and cooling setpoints are changed simult...

Page 22: ...use this selection option 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxiliary functions via a separate and dedi...

Page 23: ...e acting 0 to 100 10 to 0 VDC DA Direct acting 0 to 100 0 to 10 VDC Reheat Sets the duty cycle time for reheat output if Option 2 3 or 5 is chosen in the SeqOpera parameter Default 0 1 10 seconds six...

Page 24: ...y sensing capability 5 TEC 6H PIR Accessory Cover can be used to replace the existing cover on a non PIR TEC20x6H 4 Series Thermostat Controller to provide occupancy sensing capability TEC20x6 H 4 and...

Page 25: ...le E27734 CCN XAPX Under UL 873 Temperature Indicating and Regulating Equipment FCC Compliant to Part 15 247 Regulations for Low Power Unlicensed Transmitters Transmitter FCC Identification pending Ca...

Reviews: