background image

TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification 
Capability, Fan Control, and Occupancy Sensing Capability 

10

If the thermostat is in Cooling demand:

the chilled water valve opens to 100%

the thermostat stages Heating to maintain the room 
temperature at the Cooling setpoint, as sensed by 
the thermostat

If the thermostat is in Cooling demand and the room 
temperature rises 2F°/1C° above the Cooling setpoint, 
the thermostat automatically disables dehumidification 
operation. Likewise, if the thermostat is in Cooling 
demand and the room temperature falls below the 
current Heating setpoint, the thermostat disables 
dehumidification operation. 

Occupancy Sensor Operation – 
TEC20x6H-4+PIR Series Thermostat 
Controllers

A TEC20x6H-4+PIR Series Thermostat Controller–or a 
TEC20x6(H)-4 Series Thermostat Controller equipped 
with a PIR accessory cover–provides advanced 
occupancy logic.

Note:

The PIR strategy is an occupied strategy. If the 

thermostat controller is programmed to be Unoccupied, 
the PIR function does not have an effect on the 
occupancy strategy.

The thermostat controller automatically switches 
occupancy levels from Occupied to Stand-By and 
Unoccupied as required, when local movement is 
sensed.

Occupancy sensing is enabled only if a PIR cover is 
installed on the thermostat controller (PIR models) or if 
a remote input is configured as a remote PIR sensor 
(

MotionNO

 or 

MotionNC

).

PIR Warm-Up Period

When a PIR cover is used and a thermostat controller 
is powered up, there is a 1-minute warm-up period 
before any local movement can be detected and 
acknowledged by the PIR sensing device. The local 
status LEDs for the PIR function are not active, and the 
sensor is in Stand-By mode for the 1-minute period. 
The PIR functionality and local movement status LEDs 
are activated after the 1-minute warm-up period has 
elapsed after the initial powering of the thermostat 
controller. If movement is present, the mode changes 
to Occupied.

PIR Diagnostic LEDs

The diagnostic LEDs inside the PIR lens brighten when 
movement is detected within the first 30 minutes after 
powerup. The LEDs do not light up or brighten after the 
initial 30-minute period.

Setpoints

The Stand-By setpoints are under the same limitations 
and restrictions as the Occupied and Unoccupied 
setpoints. Stand-By setpoints reside between the 
corresponding Occupied and Unoccupied setpoint 
values.

The installer must be certain that the difference 
between the Stand-By and Occupied values can be 
recovered within a timely fashion to ensure occupancy 
comfort. In addition, the difference between the two 
values must be large enough to warrant maximum 
energy savings. 

Hotel and lodging applications can benefit from the 
addition of an entry door switch wired to one of the 
binary inputs of the thermostat controller. When a door 
contact is used and configured, the Stand-By timer and 
its configuration are no longer active or used. The 
occupancy toggle between Occupied and Stand-By is 
then dictated by both the door contact and the 
PIR sensing device used. If movements are detected 
by the PIR sensor and the door is closed, the room is 
considered occupied. The thermostat controller 
switches back to Stand-By mode only if the door switch 
toggles open/closed. Motion is ignored when the door 
switch indicates an open door.

PIR occupancy functionality is dictated by both the 
Stand-By timer and Unoccupied timer configuration 
value and movements present in the area.

Unoccupied Timer Disable

It might be preferable for the local area to stay out of 
Unoccupied mode and always stay at the Stand-By 
occupancy level when no activity is present. In 
instances when areas always need to be on Stand-By 
status, ready to respond to demand at any given point 
in time, we recommend disabling the Unoccupied timer. 
When the local PIR occupancy routine is running at the 
thermostat controller, the zone drifts into Unoccupied 
mode when the Unoccupied timer is set above its 
factory default value of 0.0 hours. 

For more information on occupancy sensor operation, 
refer to the 

TEC2x45-4, TEC2xx6(H)-4, 

TEC2xx6H-4+PIR, and TEC2xx7-4 Series Thermostat 
Controllers Application Note (LIT-12011594). 

Summary of Contents for TEC20x6-4 Series

Page 1: ...less Thermostat Controllers are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or p...

Page 2: ...Metasys System Location Guide LIT 12011294 Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Page 3: ...u have enough space for cabling and end of line devices if needed Note For surface mount applications use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the m...

Page 4: ...ire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB Note I...

Page 5: ...EC20x6H 4 PIR Series Thermostat Controller Terminals Figure 6 TEC20x6 H 4 and TEC20x6H 4 PIR Series Thermostat Controller with Separate Power Source for Auxiliary Contact FIG TEC20x6H4_SEP BI2 UI3 BI1...

Page 6: ...Aux BO5 Aux BO5 Aux Auxiliary Binary Output 8 BO3 BO3 Blank Open Heat 9 Blank BO4 AO2 Close Heat 10 Blank BO1 AO1 Open Cool 11 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 R...

Page 7: ...ting Valve 24 V Hot BO3 N C Cooling Valve FIG TEC2016H4_onoff Figure 9 Wiring TEC2026 H 4 TEC2026H 4 PIR TEC2036 H 4 and TEC2036H 4 PIR Thermostat Controllers for On Off Control Two Pipe Applications...

Page 8: ...key also allows access to the Installer Configuration Menu See the Configuring the Thermostat Controller section C F key hospitality models changes the temperature scale to either Celsius or Fahrenhe...

Page 9: ...te For models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current...

Page 10: ...tic LEDs The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup The LEDs do not light up or brighten after the initial 30 minute period Se...

Page 11: ...he UP DOWN arrow keys to choose the desired selection option 4 Press and release the center key to continue scrolling through the parameters St By Heat 69 F Occ Heat 72 F Occ Cool 75 F St By Cool 78 F...

Page 12: ...ration SeqOpera Choose the appropriate sequence of operation The modes presented are user dependent on the sequence of operation selected For two pipe applications using a changeover sensor choose the...

Page 13: ...Cooling with Reheat See Figure 18 6 and 7 Reheat 10 N O Cooling 11 N C Cooling 6 and 7 Reheat 10 Open Cooling 11 Closed Cooling 6 and 7 Reheat 10 Proportional Cooling 3 Heating with Reheat See Figure...

Page 14: ...Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling...

Page 15: ...tting Figure 22 This operation applies to the occupied mode when the fan is set to Auto Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Device Closed Device Opened Cooling Se...

Page 16: ...e fan to low speed the chilled water valve opens to the specified maximum value set by CoolMax the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint as sens...

Page 17: ...ted if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan mode A window alarm appears indicating that the window needs to be closed to resume heating or cooling These settings dis...

Page 18: ...mperature is available as a point for integration and UI3 Status is not available as a point for integration MenuScro Gives the option of having the display continuously scroll the parameters Default...

Page 19: ...Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a changeover sensor to allow changeo...

Page 20: ...from drifting from stand by mode to unoccupied mode when occupancy sensor functions are used Range 0 0 to 24 0 hours in 0 5 hour increments St By HT Sets Stand by heating setpoint when used with occu...

Page 21: ...int Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use Both the heating and cooling setpoints are changed simult...

Page 22: ...use this selection option 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxiliary functions via a separate and dedi...

Page 23: ...e acting 0 to 100 10 to 0 VDC DA Direct acting 0 to 100 0 to 10 VDC Reheat Sets the duty cycle time for reheat output if Option 2 3 or 5 is chosen in the SeqOpera parameter Default 0 1 10 seconds six...

Page 24: ...y sensing capability 5 TEC 6H PIR Accessory Cover can be used to replace the existing cover on a non PIR TEC20x6H 4 Series Thermostat Controller to provide occupancy sensing capability TEC20x6 H 4 and...

Page 25: ...le E27734 CCN XAPX Under UL 873 Temperature Indicating and Regulating Equipment FCC Compliant to Part 15 247 Regulations for Low Power Unlicensed Transmitters Transmitter FCC Identification pending Ca...

Reviews: