TE-6300M Series Well Insertion Temperature Sensors Installation Instructions
1
Refer to the
QuickLIT website
for the most up-to-date version of this document.
Applications
Installation
Dimensions
Mounting
Location Considerations
Consider the following mounting location guidelines:
•
Avoid areas subject to the effects of excessive
vibration, electrical noise, direct sunlight, or radiant
heat.
•
Keep electrical wiring as short as possible to
minimize temperature error.
Mounting the Temperature Sensor
See Figure 2 and mount the temperature sensor:
IMPORTANT:
The TE-6300M Series Well Insertion
Temperature Sensors are intended to provide an
input to equipment under normal operating
conditions. Where failure or malfunction of the
sensor could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the sensor.
IMPORTANT :
Le TE-6300M Series Well Insertion
Temperature Sensor est destiné à transmettre des
données entrantes à un équipement dans des
conditions normales de fonctionnement. Lorsqu'une
défaillance ou un dysfonctionnement du sensor
risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du sensor.
IMPORTANT:
Do not install the TE-6300M Series
Well Insertion Temperature Sensor in ambient
temperatures beyond the specified -50 to 220°F
(-46 to 104°C) temperature range. Installing the
temperature sensor in ambient temperatures
beyond this range may damage the unit and void the
warranty.
Figure 1: Sensor Dimensions, in. (mm)
F
IG
:
sn
s_
d
im
1.80 (45.7)
0.875
(22.2)
Side View
1.20
(30.5)
1.87 (47.5)
1.87
(47.5)
0.60 (15.2)
Front View
4.73 (120.1) maximum
7.73 (196.3) maximum
Figure 2: Installing the Well Insertion Sensor
F
IG
:
s
n
s
_
in
s
t
or
Sensor
Probe
TE-6300W-101
TE-6300W-102
Thermowell
Direct Mount for
6 in. (152 mm) Probe Models
Set Screw
1/2 in.
NPT
Threaded Mount for
8 in. (203 mm) Probe Models
Well Adaptor
Set Screw
TE-6300W-110 Thermowell
TE-6300M Series Well Insertion Temperature Sensors
Installation Instructions
TE-631xM, TE-635xM,
TE-634xM, TE-636xM
Part No. 24-4034-182, Rev. G
Issued March 2016
2 4 - 4 0 3 4 - 1 8 2 , Re v . G