166349-BIM-E-1008
Johnson Controls Unitary Products
3
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's
expense.
Size of unit for proposed installation should be based on heat
loss/heat gain calculations made in accordance with industry
recognized procedures identified by the Air Conditioning
Contractors of America.
Figure 1: Component Location
Unit Location
Several important factors must be considered before selecting
the site for this unit:
1.
Site – Select a solid level position, preferably on a concrete
slab, slightly above grade level and parallel to the home.
2.
Proximity to home or building – The length of the supply
and return ducts should be kept to a minimum with no
sharp bends. Consideration should be given to the
distance and routing of electrical service to connect the
unit. Try to select a site for the unit that it is as close as
possible to the proposed return grille location. Unit may be
positioned to draw air from underneath structure.
Direct Drive
Condenser Fan Motor
Decorative Protective
Coil Guard
Heavy Gauge
Base Rails
Control Box Service
Access Panel
Refrigerant
Connections
X13 Direct Drive
Blower Motor
Blower Service
Access Panel
High Efficiency Enhanced
Copper Tube/Aluminum Fin
Outdoor Coil
High Efficiency Enhanced
Copper Tube/Aluminum Fin
In
door Coil
High Efficiency
Compressor Rigidly
Mounted
Table 1:
Unit Limitations
Size
(Tons)
Unit Voltage
Unit Limitations
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
024
(2.0)
208/230-1-60
187
252
125
030
(2.5)
208/230-1-60
187
252
125
036
(3.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
042
(3.5)
208/230-1-60
187
252
125
048
(4.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
060
(5.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125