5538117-UIM-B-0319
Johnson Controls Ducted Systems
9
TABLE 8:
Electrical Data for 230-3-60 Multi Source Power
Model
Compressor
OD Fan
Motor
Blower
Motor
Electric Heat Option
Multi Source
Heater Kit
Heater kW
Stages
Heater Amps
RLA
LRA
MCC
FLA
FLA
230
230
230
230
230
230
230
230
Multi Source: Compressor
Circuit and Heat Circuits
Multi Source:
Circuit #1 Compressor Circuit
Circuit #2 Heat
Circuit #3 Heat
MCA
1
Amps
MOP
2
MCA
1
Amps
MOP
2
MCA
1
Amps
MOP
2
Circuit #1
Circuit #2
Circuit #3
PCE4A36 10.4
73.0
16.3
1.3
3.8
none
--
--
--
18.1
25
--
--
--
--
6HK06501025
8.8
1
22.1
18.1
25
27.7
30
--
--
6HK06501525
13.2
1
33.2
18.1
25
41.5
45
--
--
PCE4B48 13.7
83.1
21.4
1.7
5.4
none
--
--
--
24.2
35
--
--
--
--
6HK06501025
8.8
1
22.1
24.2
35
27.7
30
--
--
6HK06501525
13.2
1
33.2
24.2
35
41.5
45
--
--
6HK06501825
15.9
2
39.9
24.2
35
49.8
50
--
--
6HK16502025
17.6
2
44.3
24.2
35
27.7
30
27.7
30
PCE4B60 16.0
110.0
24.9
1.7
7.0
none
--
--
--
28.7
40
--
--
--
--
6HK06501025
8.8
1
22.1
28.7
40
27.7
30
--
--
6HK06501525
13.2
1
33.2
28.7
40
41.5
45
--
--
6HK06501825
15.9
2
39.9
28.7
40
49.8
50
--
--
6HK16502025
17.6
2
44.3
28.7
40
27.7
30
27.7
30
6HK16502525
22.0
2
55.3
28.7
40
34.6
35
34.6
35
1. MCA = Minimum Circuit Ampacity.
2. MOP = Maximum Over Current Protection device; must be HACR type circuit breaker or time delay fuse.