Technical specifications
Table 10: PCA3613 Advanced Application Programmable Controller
Product Code Numbers
CH-PCA3613-0 Advanced Application Programmable Controller
Note:
This model is currently only available in Asia and the
Middle East.
Power Requirement
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz,
power supply Class 2 (North America), Safety Extra-Low Voltage
(SELV) (Europe)
Power Consumption
14 VA maximum
Note:
The VA rating does
not
include any power supplied
to the peripheral devices connected to binary outputs (BOs)
or configurable outputs (COs), which can consume up to 12
VA for each BO or CO; for a possible total consumption of an
additional 72 VA (maximum).
Power Source
+15 VDC power source terminals provide 100 mA total current.
Quantity 2 located in Universal IN terminals - for active (3-wire)
input devices
Ambient Conditions
Operating:
0°C to 50°C (32°F to 122°F); 10% to 90% RH
noncondensing
Storage:
-40°C to 80°C (-40°F to 176°F); 5% to 95% RH
noncondensing
Controller Addressing for
BACnet MS/TP
DIP switch set; valid controller device addresses 4–127 (Device
addresses 0–3 and 128–255 are reserved and not valid controller
addresses.)
Controller Addressing for N2
DIP switch set; valid control device addresses 1-254
Communications Bus
Selectable N2 or BACnet
®
MS/TP, RS-485:
3-wire FC Bus between the supervisory controller and other
controllers
4-wire SA Bus between controller, network sensors and other
sensor/actuator devices, includes a lead to source 15 VDC supply
power (from controller) to bus devices.
Processor
RX631 32-Bit Renesas
®
microcontroller
Memory
16 MB flash memory and 8 MB RAM
Real-Time Clock Backup
Power Supply
Super capacitor maintains power to the onboard real-time clock
for a minimum of 72 hours when supply power to the controller
is disconnected.
PCA3613 Advanced Application Programmable Controller Installation Instructions
28