Commissioning the Controllers
You commission BACnet MS/TP controllers with the Controller Configuration Tool (CCT) software,
either via a Bluetooth
®
Wireless Commissioning Converter, a ZFR wireless dongle, or in
BACnet router mode when connected to an Supervisory Controller. Refer to
Controller Tool Help
(LIT-12011147)
for detailed information on commissioning controllers.
Note:
The MAP Gateway serves as a replacement for the BTCVT, which is no longer available
for purchase, but continues to be supported.
Troubleshooting the Controllers
Observe the Status LEDs on the front of the field controller and see the table below to troubleshoot
the controller. To troubleshoot an integral or local controller display, refer to the
FX-DIS Local
Controller Display Technical Bulletin (LIT-12011666)
.
LED status and states
Table 8: Status LEDs and description of LED states
LED label
LED
color
Normal LED
state
Description of LED states
POWER
Green
On Steady
Off Steady = No Supply Power or the controller’s
polyswitch/resettable fuse is open. Check Output wiring for
short circuits and cycle power to controller.
On Steady = Power Connected
FAULT
Red
Off Steady
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main
Code download required.
Blink - 2 Hz = Download or Startup in progress, not ready
for normal operation
SA BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not
supported)
On Steady = Communication lost, waiting to join
communication ring
PCA3613 Advanced Application Programmable Controller Installation Instructions