Installation Guide
FCU Controller
16
INPUT 2 (I2) - MIXED AIR TEMPERATURE WIRING
Input 2 must be wired to the Mixed Air Temperature. Wiring for I2 is shown
in Figure 9. To wire I2 to a thermistor:
1
. Select the correct jumper setting for a thermistor on
J8
.
2
. Connect one lead of the thermistor to input terminal
I2
on terminal
block
J2
.
3
. Connect the other lead to one of the
GND
terminals.
NOTE:
Only a 10K Type II (CP Curve) thermistor may be used.
J9
J8
J4
J5
J6
J7
J8
J9
J2
THERMISTOR
GND I5
I4 GND I3 I2
VOUT
I1
GND
I6
Figure 9. I2 - Thermistor Wiring.