FANs 125, 121   

 

Temperature Controls Section 

A

 

 

Installation Bulletin   

 

Issue Date  1199 

©  1999 Johnson Controls, Inc. 

 

1

 

  Part No. 24-7664-1725, Rev. A 

www.johnsoncontrols.com 

  Code No. LIT-125209

 

 
 

IMPORTANT: 

All MS2 controls are designed for 
use 

only

 as operating controls. 

Where an operating control 
failure would result in personal 
injury or loss of property, it is the 
responsibility of the installer to 
add devices (safety, limit 
controls) or systems (alarm, 
supervisory systems) that protect 
against, or warn of, control 
failure. 

 

Refer to the 

MS Series Multi-Stage Electronic 

Temperature Controls Product Bulletin, LIT-125198,

 for 

necessary information on operation and performance 
specifications for this product. 

M

ounting 

The MS2 control is not position-sensitive but should be 
mounted for convenient wiring and adjustment. 

To mount the DIN Rail Mount version, install the DIN 
rail where appropriate. Snap the control onto the rail in 
position. 

To mount the Panel Mount version, ensure that there is 
sufficient space behind the panel. At least  
2-3/4 inches (70 mm) are needed. Make a cutout  
1-3/16 by 2-13/16 inches (29 by 71 mm). Remove 
retaining clip from control. Insert the control into the 
hole. Install retaining clip and adjust for tightness. 

W

iring 

!

WARNING: 

Risk of Electrical Shock. 

Disconnect power supply before 
making electrical connections to 
avoid possible electrical shock or 
equipment damage. 

 

Follow these wiring guidelines: 

 

All wiring must conform to the National Electric 
Code and local regulations. 

 

Make all wiring connections using adequate gauge 
copper conductors only. Connectors are rated for 
14-22 AWG wiring. 

SC

D

V1 V2

Internal to Control

Process
Sensor

Binary

Input

Binary and Sensor Common

Power
Supply

C1

C2

Stage 

 

Stage 

Refer to Rating Table for more information.

Terminal Not Used

 

Figure 1: MS2 Panel Mount Wiring  

Internal to Control

Process

Sensor

Binary 

Input

Stage

Stage

Power 

Supply

V1 V2

CD

C1

SC

C2

S1

D

Sensor Common

Binary
Common

Terminal Not Used

Refer to Rating Table for more information.

 

Figure 2: MS2 DIN Rail Mount Wiring  

I

NSTALLATION 

B

ULLETIN

 

 

MS2 Two Stage Electronic Temperature Control 

Summary of Contents for MS2

Page 1: ... version ensure that there is sufficient space behind the panel At least 2 3 4 inches 70 mm are needed Make a cutout 1 3 16 by 2 13 16 inches 29 by 71 mm Remove retaining clip from control Insert the control into the hole Install retaining clip and adjust for tightness Wiring WARNING Risk of Electrical Shock Disconnect power supply before making electrical connections to avoid possible electrical ...

Page 2: ...input status On or OF After 15 seconds of inactivity the display shows the process temperature Setting Up the Stage Control To lock unlock the unit for programming Press the Enter Up and Down buttons simultaneously and hold until is displayed Hold for about 10 seconds until the current temperature is displayed This toggles the keypad between locked and unlocked To run the self test procedure IMPOR...

Page 3: ...A MS2 Two Stage Electronic Temperature Control Installation Bulletin 3 value it is not saved The control reverts to the old value ...

Page 4: ... degrees 10 AH High Temperature Alarm High temperature alarm setpoint relative to main setpoint 0 to 50F 0 to 50C above setpoint 15 AL Low Temperature Alarm Low temperature alarm setpoint relative to main setpoint 50 to 0F 50 to 0C below setpoint 15 Ad Alarm Differential Temperature difference relative to high and low alarms at which alarm output is switched Off 1 to 9F 1 to 9C 5 At Alarm Time Del...

Page 5: ...set Ordering Information Table 6 Specifications Power Requirements 3 7 VA 24 VAC 50 60 Hz Class 2 20 30 VAC Ambient Conditions Operating 14 to 140 F 10 to 60 C 0 to 95 RH non condensing Storage 22 to 176 F 30 to 80 C 0 to 95 RH non condensing Accuracy 1 8 F 1C Agency Listings UL Recognized File E194024 CCN XAPX2 Canadian UL Recognized File E194024 CCN XAPX8 FCC Compliant per Class A Digital Device...