SECTION 8 – SERVICE
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
8
TABLE 52 -
FAULTS LOCKOUT
HISTORY
SCREEN WORD-
ING
DESCRIPTION
RESET
SHOW WHEN
UNIT TYPE IS
STATUS
SCREEN
WORDING
FAULT
OUTPUT
TYPE
Lockout-Com-
pressor System *
Time Out
See below
System
Lockout
Comp System *
- Safety Lockout
Alarm
Lockout -
Compressor
System *
High press switch, comp motor protec-
tor, or overcurrent protector open - 3
times in 120 minutes on comp system *
System
Lockout
Comp System *
- Safety Lockout
Alarm
Lockout-High
Duct Pressure
Duct static press c duct static
over pressure
Unit
Lockout
UNIT TYPE is VAV
or FLEXSYS
Supply Sys
Status Safety
Lockout
Alarm
Lockout - Hot
Water Freeze
The hydronic freeze stat switch
remained closed greater than or equal
to 5 minutes
Unit
Lockout
Heat Type HOT
WATER/STEAM
Heating Sys
Status - Safety
Lockout
Alarm
Lockout - Low
Press Sys *
The suction pressure is below the suc-
tion pressure limit and the increment-
ing timer has timed out
System
Lockout
Always
Compressor
System
Status Low
Press Lockout
Alarm
Lockout -
Manual Stop *
The compressor system has been
placed in the stop mode either through
the user interface or by a
communicated input
System
Lockout
Comp Sys *
Status Disabled
Lockout - Manual
Unit Stop
The unit is shut down through the shut
down switch on the unit or by an exter-
nal hardwired or communicated input
Unit
Lockout
Unit - Overall
Status Local
Stop
Lockout -
Sat Sensor
Supply air temp current sensor is out
of range for greater than or equal to 10
seconds
Unit
Lockout
UNIT TYPE is
CONSTANT
VOLUME or
VARIABLE AIR
VOLUME
Alarm
Lockout-
Supply Fan
Supply fan proving switch failed to
close within 120 seconds of supply fan
start, or the supply fan proving switch
opened for more than 10 seconds dur-
ing operation
Unit
Lockout
Unit - Overall
Status Unit
Lockout
Alarm
NOTES:
Can be A-F compressors.
“WRN - COMP SYSTEM * INHIBIT” - This WARNING indicates the compressor system safety circuit experienced a trip but reset prior to the
exploration of the 60 minute reset time function. If the safety circuit does not reset in 60 minutes it is replaced with a “LOCKOUT - COMPRES-
SOR SYSTEM * TIME OUT” message.
“AUTO RESET - COMPRESSOR SYSTEM * CLEAR” - When there is a compressor safety trip the Primary Unit Controller initiates the
“COMPR STATUS CLEAR TIME *” timer. The Primary Unit Controller records the time it takes for the trip to clear. When the fault clears “COM-
PRESSOR SYSTEM * CLEAR” shows the time it took for the fault to clear in the HISTORY buffer.
“LOCKOUT-COMPRESSOR SYSTEM * TIME OUT” – If the “COMPR STATUS CLEAR TIME *” timer reaches 60 minutes a “LOCKOUT -
COMPRESSOR SYSTEM * TIME OUT” is indicated in the HISTORY buffer.
See page 13 for minimum CFM setpoints to assure closure of the supply fan proving switch.