5808011-JIM-A-0320
Johnson Controls Ducted Systems
77
Table 36: J08ZB charging table - system 1
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction temp.
Discharge
pressure
Liquid temp.
Delta T Db
Entering evap
Db
300 Cfm/Ton
80/62
75
145
62
269
269
-25
7.4
85
144
60
314
314
-26
8.2
95
143
58
359
359
-26
9.1
300 Cfm/Ton
79.82/66.95
75
144
61
268
268
-25
7.4
85
146
61
315
315
-24
8.3
95
148
61
363
363
-24
9.2
300 Cfm/Ton
80/72
75
142
60
266
266
-25
7.4
85
148
62
317
317
-23
8.4
95
154
63
367
367
-21
9.3
300 Cfm/Ton
75/62
75
139
59
267
267
-23
7.4
85
139
57
314
314
-23
8.3
95
139
56
361
361
-22
9.1
400 Cfm/Ton
80/62
75
151
66
270
270
-23
7.4
85
151
64
316
316
-22
8.3
95
152
62
362
362
-22
9.1
400 Cfm/Ton
80.005/66.92
75
150
65
269
269
-23
7.5
85
152
64
316
316
-22
8.3
95
154
63
363
363
-21
9.2
400 Cfm/Ton
80/72
75
149
63
269
269
-22
7.5
85
153
63
316
316
-21
8.4
95
156
64
364
364
-20
9.3
400 Cfm/Ton
75/62
75
144
62
268
268
-20
7.4
85
145
60
315
315
-20
8.3
95
146
59
363
363
-19
9.2
Table 37: J08ZB charging table - system 2
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction temp.
Discharge
pressure
Liquid temp.
Delta T Db
Entering evap
Db
300 Cfm/Ton
80/62
75
143
467
277
83
-25
7.1
85
143
467
321
91
-26
7.9
95
144
468
365
99
-26
8.7
300 Cfm/Ton
79.82/66.95
75
141
466
274
82
-25
7.0
85
144
465
320
90
-24
7.9
95
147
465
367
98
-24
8.8
300 Cfm/Ton
80/72
75
139
464
272
82
-25
6.9
85
144
463
320
90
-23
7.9
95
150
463
368
97
-21
8.9
300 Cfm/Ton
75/62
75
135
465
276
81
-23
7.1
85
137
466
321
89
-23
7.9
95
139
467
366
98
-22
8.8
400 Cfm/Ton
80/62
75
149
466
278
83
-23
7.1
85
151
466
322
91
-22
7.9
95
153
467
367
100
-22
8.8
400 Cfm/Ton
80.005/66.92
75
148
464
276
82
-23
7.1
85
151
465
322
90
-22
7.9
95
154
466
367
98
-21
8.8
400 Cfm/Ton
80/72
75
147
463
275
82
-22
7.0
85
151
464
321
89
-21
7.9
95
154
465
368
97
-20
8.8
400 Cfm/Ton
75/62
75
142
465
276
81
-20
7.1
85
145
465
321
90
-20
7.9
95
147
466
366
98
-19
8.8