Table 7: Status LEDs and description of LED states

LED label

LED color Normal LED

state

Description of LED states

POWER

Green

On Steady

Off Steady = No Supply Power. The expansion module’s

polyswitch/resettable fuse may be open. Check output wiring for

short circuits and cycle power to expansion module.

On Steady = Power Connected

FAULT

Red

Off Steady

Off Steady = No Faults

On Steady = Device Fault

Blink - 2 Hz = Download or Startup in progress: not ready for

normal operation

SA/FC BUS

Green

Blink - 2 Hz

Blink - 2 Hz = Data Transmission (normal communication)

Off Steady = No Data Transmission (N/A - auto baud not

supported)

On Steady = Communication lost; waiting to join communication

ring

EOL

Amber

Off (Except on

terminating

devices)

On Steady = EOL switch in ON position

Off Steady = EOL switch in Off position

Repair information

If a controller fails to operate within its

specifications, replace the controller. For a

replacement controller, contact your Johnson

Controls representative.

Accessories

Table 8: Accessories Ordering Information

Product Code Number Description

Mobile Access Portal

(MAP) Gateway

Refer to the 

Mobile Access Portal Gateway Catalog Page (LIT-1900869)

 to identify the

appropriate product for your region.

Note: 

The MAP Gateway serves as a replacement for the BTCVT, which is no

longer available for purchase, but continues to be supported.

TL-CCT-0

Metasys

 Controller Configuration Tool (CCT) Software

MS-FCP-0

Metasys

 Field Controller Firmware Package Files for CCT

TP-2420

Transformer, 120 VAC Primary to 24 VAC Secondary, 20 VA, Wall Plug

Y65T31-0

Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8

in. Primary Leads and Secondary Screw Terminals, Class 2

Note: 

Additional Y6x-x Series transformers are also available. Refer to the

Series Y63, Y64, Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755)

 for

more information.

AS-CBLTSTAT

Cable adapter for connection to 8-pin TE-6700 Series sensors

AS-XFR050-0

Power Transformer (Class 2, 24 VAC, 50 VA Maximum Output), no enclosure

AP-TBK4SA-0

Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk Pack of 10

IOM3733 Input/Output Module Installation Guide

12

Summary of Contents for IOM3733

Page 1: ...e pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipmen...

Page 2: ...Observe these guidelines when mounting a controller Ensure the mounting surface can support the controller DIN rail and any user supplied enclosure Mount the controller horizontally on 35 mm DIN rail...

Page 3: ...op of the DIN rail channel on the back of the controller and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To...

Page 4: ...ortant Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed inf...

Page 5: ...ock Wiring Note The supply power wire colors may be different on transformers from other manufacturers Refer to the transformer manufacturer s instructions and the project installation drawings for wi...

Page 6: ...output cables Shielded cable is required for input and output cables that are exposed to high electromagnetic or radio frequency noise Inputs or outputs with cables less than 30 m 100 ft typically do...

Page 7: ...es for low voltage 30 V inputs and outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded...

Page 8: ...terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements required cable type FC or SA Bus Communications COM Signal...

Page 9: ...s Table 5 Termination details Type of device Type of Input Output Termination diagrams Dry Contact Binary Input BI Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output...

Page 10: ...but do not interfere with bus operation Set a valid and unique device address on the expansion module before applying power to the expansion module on the bus To set the device addresses on Metasys e...

Page 11: ...r to the MS TP Communications Bus Technical Bulletin LIT 12011034 3 If the controller is a terminating device on the FC bus set the EOL switch to ON If the controller is not a terminating device on th...

Page 12: ...ve Accessories Table 8 Accessories Ordering Information Product Code Number Description Mobile Access Portal MAP Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify...

Page 13: ...Product Code Number Description AP TBK4FC 0 Replacement FC Bus Terminal Blocks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 IOM3733 In...

Page 14: ...er 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module...

Page 15: ...2 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact informatio...

Page 16: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: