Technical specifications

Table 9: IOM3731-0A technical specifications

Product Code Number

MS-IOM3731-0A Input/Output Expansion Module

Note: 

This model is only available in certain regions. Contact your local Johnson

Controls representative for more information.

Power Requirement

24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2

(North America), Safety Extra-Low Voltage (SELV) (Europe)

Power Consumption

14 VA maximum

Ambient Conditions

Operating:

 0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensing

Storage:

 -40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing

Addressing

DIP switch set; valid expansion module device addresses 4–127 (Device addresses 0–3 and

128–255 are reserved and not valid expansion module addresses.)

Communications Bus

BACnet MS/TP, RS-485:

3-wire FC bus between the supervisory controller and expansion modules (for MS/TP bus

communications at 38,400 baud)
4-wire SA bus between expansion module, network sensors and other sensor/actuator

devices, includes a lead to source 15 VDC supply power (from controller or expansion

module) to bus devices (for MS/TP bus communications at 38,400 baud)

Processor

RX631 Renesas

®

 32-bit microcontroller

Memory

4 MB external serial flash memory and 768 KB internal flash and 128 KB internal RAM

Input and Output Capabilities

8 - Binary Inputs:

 Defined as Dry Contact Maintained or Pulse Counter/Accumulator

Mode

8 - Binary Outputs:

 Defined as 24 VAC Triac (external source power only)

Terminations

Input/Output:

 Fixed Screw Terminal Blocks

SA/FC Bus and Supply Power:

 4-Wire and 3-Wire Pluggable Screw Terminal Blocks

Mounting

Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface

with three integral mounting clips on expansion module

Housing

Enclosure material:

 ABS and polycarbonate UL94 5VB; self-extinguishing, plenum-rated

Protection Class: IP20 (IEC529)

Dimensions (Height x Width x Depth)

150 mm x 164 mm x 53 mm (5-7/8 in. x 6-1/2 in. x 2-1/8 in.) including terminals and

mounting clips

Note: 

Mounting space requires an additional 50 mm (2 in.) space on top, bottom

and front face of the expansion module for easy cover removal, ventilation and wire

terminations.

Weight

0.5 kg (1.1 lb)

United States:

 UL Listed, File E107041, CCN PAZX, UL 916, Energy Management

Equipment
FCC Compliant to CFR47, Part 15, Subpart B, Class A

Canada:

 UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No. 205, Signal Equipment

Industry Canada Compliant, ICES-003

Europe:

 Johnson Controls declares that this product is in compliance with the essential

requirements and other relevant provisions of the EMC Directive.

Australia and New Zealand:

 RCM Mark, Australia/NZ Emissions Compliant

Compliance

BACnet International:

 BACnet Testing Laboratories (BTL) Protocol Revision 15 Listed and

Certified BACnet Smart Actuator (B-SA)

The performance specifications are nominal and

conform to acceptable industry standard. For

application at conditions beyond these specifications,

consult the local Johnson Controls

®

 office. Johnson

Controls shall not be liable for damages resulting from

misapplication or misuse of its products.

Product warranty

This product is covered by a limited

warranty, details of which can be found at

www.johnsoncontrols.com/buildingswarranty.

IOM3731-0A Expansion Input/Output Installation Guide

13

Summary of Contents for IOM3731-0A

Page 1: ...easonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case...

Page 2: ...nsion module Ensure the mounting surface can support the expansion module DIN rail and any user supplied enclosure Mount the expansion module horizontally on 35 mm 1 4 in DIN rail whenever possible Mount the expansion module in the proper mounting position Figure 2 Mount the expansion module on a hard even surface whenever possible in wall mount applications Use shims or washers to mount the expan...

Page 3: ...om mounting clips inward up to secure the controller on the DIN rail To remove the controller from the DIN rail pull the bottom mounting clips out to the extended position and carefully lift the controller off the DIN rail Wall mount applications To mount the controller directly on a wall or other flat vertical surface complete the following steps 1 Pull the two bottom mounting clips outward and e...

Page 4: ...mportant Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed information on configuring and wiring an MS TP Bus FC bus and SA bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 Terminal blocks and bus ports See Figure 1 for terminal block ...

Page 5: ...nding on which bus the expansion module is operating on The SA FC bus port is connected internally to the SA FC bus terminal block See for more information The SA FC bus port pin assignment is shown in Figure 6 Figure 6 Pin number assignments for sensor SA bus and FC bus ports on expansion modules Supply power terminal block The 24 VAC supply power terminal block is a gray removable 3 terminal plu...

Page 6: ...ro Series Wireless Field Bus System Product Bulletin LIT 12012320 For more information on the ZFR 1800 Wireless Field Bus system refer to the ZFR1800 Series Wireless Field Bus System Product Bulletin LIT 12011336 Terminal Wiring Guidelines Functions Ratings and Requirements Input and output wiring guidelines The following table provides information and guidelines about the functions ratings and re...

Page 7: ...es for low voltage 30 V inputs and outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire A 0 5 mm 24 AWG stranded copper 107 m 350 ft twisted wire 100 mV maximum voltage drop Depending on cable and t...

Page 8: ...size and cable length requirements for the SA and FC buses Table 4 Communications bus and supply power terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Common for FC or SA Bus communications FC BUS or SA BUS SHLD or SAPWR SHLD on FC Bus...

Page 9: ...Table 5 Termination details Type of device Type of Input Output Termination diagrams Dry Contact Binary Input BI Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output Switch Low Externally Sourced BO 24 VAC Binary Output Switch High Externally Sourced BO Incremental Control to Actuator Switch High Externally Sourced BO IOM3731 0A Expansion Input Output Installation ...

Page 10: ...r numbered switches until the total equals the intended address For example if the intended device address is 21 set switches 16 4 and 1 to ON 16 4 1 21 and all other switches to OFF 3 Set a unique and sequential device address for each of the expansion modules connected on the SA or FC bus starting with device address 4 Note To ensure the best bus performance set sequential device addresses with ...

Page 11: ... the controller is not a terminating device on the bus set the EOL switch to Off When a controller is connected to power with its EOL switch set to ON the amber EOL LED on the controller cover is lit Commissioning You commission expansion modules with the Controller Configuration Tool CCT software using NxE Passthru Bluetooth with BTCVT through Mobile Access Portal MAP Gateway at version 4 2 or ab...

Page 12: ... AS XFR050 0 Power Transformer Class 2 24 VAC 50 VA Maximum Output no enclosure AP TBK4SA 0 Replacement SA Bus Terminal Blocks 4 Position Brown Bulk Pack of 10 AP TBK4FC 0 Replacement FC Bus Terminal Blocks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 WNC1800 ZFR182x Pro Wireless field Bus System This system is used for installations...

Page 13: ...er 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module Housing Enclosure material ABS and polycarbonate UL94 5VB self extinguishing plenum rated Protection Class IP20 IEC529 Dimensions Height x Width x Depth 150 mm x 164 mm x 53 mm 5 7 8 in x 6 1 2 in x 2...

Page 14: ...SON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact information refer to www johnsoncontrols com locations 2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com ...

Reviews: