Technical specifications

Table 10: IOM2723 technical specifications

Product Code Number

MS-IOM2723-0 Input/Output Module

Note: 

This model is only available in certain regions. Contact your local Johnson

Controls representative for more information.

Power Requirement

24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2

(North America), Safety Extra-Low Voltage (SELV) (Europe)

Power Consumption

14 VA maximum

Ambient Conditions

Operating:

 0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensing

Storage:

 -40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing

Addressing

DIP switch set; valid expansion module device addresses 4–127 (Device addresses 0–3 and

128–255 are reserved and not valid expansion module addresses)

Communications Bus

BACnet MS/TP, RS-485:

3-wire FC Bus between the supervisory controller and other controllers or expansion

modules (for MS/TP bus communications at 38,400 baud)
4-wire SA Bus between expansion module, network sensors and other sensor/actuator

devices, includes a lead to source 15 VDC supply power (from controller or expansion

modules) to bus devices (for MS/TP bus communications at 38,400 baud)

Processor

RX631 Renesas

®

 32-bit microcontroller

Memory

4 MB external serial flash memory and 768 KB internal flash and 128 KB internal RAM

Input and Output Capabilities

8 - Universal Inputs:

 Defined as 0–10 VDC, 4–20 mA, 0–600k ohm, or Binary Dry Contact

2 - Analog Outputs:

 Defined as 0–10 VDC or 4–20 mA

Analog Input and Output Resolution and

Accuracy

Input: 

15-bit resolution

Output: 

15-bit resolution, +/-200 mV accuracy in 0–10 VDC applications

Terminations

Input/Output:

 Fixed Screw Terminal Blocks

SA/FC Bus and Supply Power:

 4-Wire and 3-Wire Pluggable Screw Terminal Blocks

Mounting

Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface

with three integral mounting clips on expansion module

Housing

Enclosure material:

 ABS and polycarbonate UL94 5VB; self-extinguishing, plenum-rated

Protection Class: IP20 (IEC529)

Dimensions (Height x Width x Depth)

150 mm x 164 mm x 53 mm (5-7/8 in. x 6-1/2 in. x 2-1/8 in.) including terminals and

mounting clips

Note: 

Mounting space requires an additional 50 mm (2 in.) on top, bottom, and

front face of expansion module for easy cover removal, ventilation, and wire

terminations.

Weight

0.5 kg (1.1 lb)

United States:

 UL Listed, File E107041, CCN PAZX, UL 916, Energy Management

Equipment
FCC Compliant to CFR47, Part 15, Subpart B, Class A

Canada:

 UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal Equipment

Industry Canada Compliant, ICES-003

Europe:

 Johnson Controls declares that this product is in compliance with the essential

requirements and other relevant provisions of the EMC Directive.

Compliance

Australia and New Zealand:

 RCM Mark, Australia/NZ Emissions Compliant

BACnet International Compliance

BACnet International:

 BACnet Testing Laboratories (BTL) Protocol Revision 15 Listed and

Certified BACnet Smart Actuator (B-SA)

The performance specifications are nominal and

conform to acceptable industry standard. For

application at conditions beyond these specifications,

consult the local Johnson Controls

®

 office. Johnson

IOM2723 Input/Output Module Installation Guide

17

Summary of Contents for IOM2723

Page 1: ...sonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed an...

Page 2: ...e can support the expansion module DIN rail and any user supplied enclosure Mount the expansion module horizontally on 35 mm DIN rail whenever possible Mount the expansion module in the proper mountin...

Page 3: ...tion shown in Figure 2 2 Pull the two bottom mounting clips outward from the expansion module to the extended position Figure 3 3 Hang the expansion module on the DIN rail by the hooks at the top of t...

Page 4: ...a on incor recte risquent d endommager irr m diablement l quipement Important Do not exceed the expansion module electrical ratings Exceeding expansion module electrical ratings can result in permanen...

Page 5: ...ray removable 3 terminal plug that fits into a board mounted jack on the top right of the expansion module Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the t...

Page 6: ...outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables regardless of wire size or number of wires should consist of stranded insulated and twisted...

Page 7: ...inum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 10k JCI Type II 2 252k Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1...

Page 8: ...re See Figure 7 to determine cable length Use twisted wire cable N A Maximum cable length versus load current Use the following figure to estimate the maximum cable length relative to the wire size an...

Page 9: ...IOM expansion module does not supply 15 VDC The SA bus supervisor supplies 15 VDC to devices on the SA bus requiring power FC Bus 0 6 mm 22 AWG stranded 3 wire twisted shielded cable required SA Bus 0...

Page 10: ...applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal...

Page 11: ...grams Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI 0 10 VDC Output to Actuator External Source AO 0 10 VDC Out...

Page 12: ...sitions of the switches on the DIP switch block at the top of the expansion module Device addresses 4 through 127 are the valid addresses for these expansion modules The following table describes the...

Page 13: ...ress is 21 set switches 16 4 and 1 to ON 16 4 1 21 and all other switches to OFF 3 Set a unique and sequential device address for each of the expansion modules connected on the SA or FC bus starting w...

Page 14: ...is a terminating device on the FC bus set the EOL switch to ON If the expansion module is not a terminating device on the bus set the EOL switch to OFF When an expansion module is connected to power w...

Page 15: ...puter server that is running CCT For additional information about the firmware package files refer to the CCT Installation Instructions LIT 12011259 Troubleshooting Observe the Status LEDs on the fron...

Page 16: ...VAC Primary to 24 VAC secondary 20 VA Wall Plug Y65T31 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Foot Mount 8 in Primary Leads and Secondary Screw Terminals Class 2 Note Additio...

Page 17: ...y Input 15 bit resolution Output 15 bit resolution 200 mV accuracy in 0 10 VDC applications Terminations Input Output Fixed Screw Terminal Blocks SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable...

Page 18: ...N CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MIL...

Reviews: