Table 5: Termination details
Type of field device
Type of Input/
Output
Termination diagrams
Analog Output
(Current)
AO
4–20 mA Output to
Actuator
AO
Voltage (Analog Output) AO
4–20 mA Output to
Actuator
AO
Setup and Adjustments
Setting the device address
Metasys
expansion modules are master devices on
MS/TP (SA or FC) buses. Before operating expansion
modules on a bus, you
must
set a valid and unique
device address for each expansion module on
the bus. You set an expansion module's device
address by setting the positions of the switches on
the DIP switch block at the top of the expansion
module. Device addresses 4 through 127 are the
valid addresses for these expansion modules.
The following table describes the FC bus and SA
bus device addresses for Johnson Controls MS/TP
communications bus applications:
Table 6: SA/FC bus device address descriptions
Device
address Use on description
0
(Switch
128 Off)
Reserved for FC Bus Supervisory
Controller (not for use on controllers or
expansion modules).
1 to 3
(Switch
128 Off)
Reserved for peripheral devices (not
for use on controllers or expansion
modules).Reserved for FC Bus
Supervisory Controller (not for use on
expansion modules).
IOM2723 Input/Output Module Installation Guide
12