Operation
Graphics Display Screen
56
IFI-WS Installation and Operation Manual – P/N LS10050-000JC-E:A 12/11/2014
5.3.3 New Events Pane
When an event is reported to the workstation, it displays the event information in the New Events pane and sounds an
audible alarm at the workstation. The workstation auto-navigates to the floor plan window that has the highest
priority event.
New events are events that have been reported to, and received by the workstation but not yet acknowledged by the
user. Once an event is acknowledged, the event either moves to the Acknowledged Events window or is removed
from the workstation.
The following may occur when new events are received:
• If the event is acknowledged at the panel, “Acked” will be displayed prefixing the event in the New Events
list.
• If the workstation has node control of the point, a colored box will display to the left of the event in the
Navigation Tree.
• If the event is unreliable (meaning it was reported while a gateway or node was in fault), an asterisk (*) will be
displayed prefixing the event in the New Events list.
5.3.3.1 New Events Buttons
The alarm acknowledge button (
✔
)
is available to all users and is displayed next to the New Events pane title. If the
workstation is configured for protected premises operating mode, then the silence and reset buttons are also available.
describes the buttons available.
Figure 5.5 Normal Acknowledge, Silence, and Reset
Item
Feature
Description
1
Alarm Acknowledge Button
Acknowledges the event.
2
Alarm Silence Button
Silences all audible alarms.
3
Reset Button
Sends reset command to the panels.
1
2
3