Alter Status
Walk Test
Figure 4.8 Clear History Screen
Soft Keys
ALARM HISTORY:
Press to clear Alarm history.
EVENT HISTORY:
Press to clear Event history.
ALL HISTORY:
Press to clear both Alarm and Event history.
4.6 Walk Test
Walk Test allows the user to test the entire fire alarm system while away from the control panel.
There are two types of Walk Test - Basic and Advanced - and each type operates in audible mode.
Walk Test results are sent to the printer and to Event History as “Test”.
IMPORTANT!
• Prior to Walk Test, secure all protected buildings, and notify the building owner/operator,
fire department, and other pertinent personnel that testing is in progress.
• Immediately after Walk Test is completed, notify the same people that testing is complete
and the system is restored to normal operation. Reconnect releasing devices.
• Walk Test will “time out” and return to normal operation after one hour when no Walk Test
activations have occurred during that time.
• Walk Test may be exited at any time by pressing the
ABORT
soft key on the screen
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I S E P 2 4 , 2 0 0 4
C L E A R H I S T O R Y
A L A R M H I S T O R Y
E V E N T H I S T O R Y
A L L H I S T O R Y
B A C K
!
WARNING:
Physically disconnect all releasing devices before starting Walk Test. It is not
sufficient to disable in any other manner.
!
WARNING:
Walk Test mode can deactivate fire protection. Observe the following important
precautions.
NOTE:
Walk Test will not start if any devices are active (i.e., fire alarms, security, supervisories
or pre-alarms.) To perform a walk test while a device is active, disable the device and press the
System Reset button.
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...