IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
21
Panel Program
Program
3.2.3 Panel Settings
Press the Panel Settings soft key on the Panel Program Menu 1 screen to choose panel settings.
Figure 3.5 Panel Settings (1) Screen
Soft Keys
LOCAL
CONTROL:
Press this soft key to toggle between Yes and No. This option disables (No) or
enables (Yes) local panel control of the Signal Silence, System Reset, and Drill Fixed Function
keys, as well as
SIGNAL
SILENCE
,
SYSTEM
RESET
, and
ACKNOWLEDGE
soft keys. A setting of
No (disable) turns the panel piezo sounder off, overriding the next field if
PIEZO
is set to ON.
Default: Yes
PIEZO:
Press this soft key to toggle between Off and On. This option enables (On) or disables
(Off) the panel piezo from sounding when alarms or troubles occur. A setting of On is overridden if
LOCAL
CONTROL
is set to No. Default: On
PROPRIETARY
SUPERVISING
STATION:
Press this soft key to enable (Yes) or disable (No)
Local Receive mode. When enabled, events and the clearing of events must be handled one at a
time: each must be acknowledged. Latching events require a system reset. The panel will override a
setting of Yes if the Node Number is greater than zero. Default: No
EVENT
ORDERING:
Press this soft key to toggle between USA and Canada ordering priorities.
This order is applied to events shown in the Multiple Events List screen. Default: USA
P A N E L S E T T I N G S
L O C A L C O N T R O L : Y E S
R E M I N D E R M E N U
P I E Z O : O N
M O R E
P R O P R I E T A R Y S U P E R V I S I N G S T A T I O N : N O
E V E N T O R D E R I N G : U S A
A C C E P T
D I S P L A Y A D D R E S S : Y E S
B A C K
NOTE:
A setting of NO (disable) will disable key switch operation.
NOTE:
ACS devices programmed for acknowledge, signal silence, system reset and drill are not
affectted by this setting: these commands will still function at the devices if LOCAL CONTROL is set to
No.
USA Event Order
Canada Event Order
Fire
Fire
Security
Supervisory
Supervisory
Trouble
Trouble
Prealarm
Prealarm
Disabled
Disabled
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...