Section 4: System operation
l
Fire alarm
l
Fail to arm
l
Alarm when armed
l
CO alarm
The maximum label size is 14 ASCII characters.
Partition command output labels
This feature is used to program custom labels for command outputs. These labels are used with output activation events in
the event buffer. The maximum label size is 14 x 2 ASCII characters. See "[201]-[208][001]-[004] Partition command output
labels" on page 77 for more details.
4.4 Annunciation
Door chime
The keypad can be programmed to use one of four different door chime tones for each zone on the system. Chime is active
only during the disarm state. Only one door chime option can be enabled for each zone.
l
Beeps
l
Bing-Bong
l
Ding-Dong
l
Alarm Tone
l
Zone Name - Voice Annunciation (HS2LCDWFVPROx keypads only)
The above door chime sounds are programmable in section [861]-[876], subsections [101]-[228].
Chime is enabled/disabled on a partition using the [*][4] command.
Temperature display
Indoor and outdoor temperature can be displayed on system keypads if configured in keypad programming section [861]-
[876]>[023] option 7, and sections [041]-[042]. Temperature is detected using wireless temperature sensors installed on the
system. Refer to "Compatible devices" on page 8.
Global keypads only display outdoor temperature.
Low temperature warning
Keypads can be configured to detect low ambient temperature.
If the temperature at the keypad drops to 6° C ± 2° C (43° F ± 3°F), the keypad zone goes into alarm. When the temperature
rises above 9° C ± 2° C (48° F ± 3° F), the keypad zone is restored.
When this option is enabled, the keypad’s zone input functionality is disabled.
Refer to section [861]-[876]>[023] option 8 for more information.
Note:
This feature has not been evaluated by UL/ULC.
- 54 -