Section 3: Configuration
3.8 Local firmware upgrade
Alarm panel firmware can be upgraded locally via DLS. Firmware upgrade prevention rules are ignored when performing a
local firmware upgrade.
To perform a local firmware upgrade:
1. Remove the front cover of the alarm panel and plug the DLS header into the micro USB connector on the alarm con-
troller.
2. Open the Flash Utility within DLS, select the latest firmware file from the Web or browse to a saved flash file on your hard
drive. Follow the steps as prompted by the Flash Utility application. A message is displayed when download is complete.
3. Once the firmware update is complete, the system powers up.
3.9 Testing the system
Installer Walk Test
Walk test enables the installer to test the operation of each detector by tripping zones, causing an actual alarm. Enter section
[901] to initiate a walk test. When a zone is tripped, all system sirens emit a tone to indicate that the zone is working correctly.
After 15 minutes without zone activity, the walk test terminates automatically. To manually exit walk test mode, enter [901]
again.
Viewing the event buffer
The event buffer contains logs of events that have occurred on the alarm system beginning with the most recent. The capa-
city of the event buffer is scalable and can hold 500/1000 events (depending on panel model) before rolling over. The buffer
displays events according to their time stamp, beginning with the most recent. The event buffer can be uploaded using DLS.
Each event displays the time and date, a description of the event, the zone label, access code number or any other pertinent
information. To view the event buffer, press [*][6][Master Code][*].